Technibel GRV79R5VAA Technical Data & Service Manual page 14

Table of Contents

Advertisement

2-2-2. Outdoor Unit
Outdoor Unit
GRV79R5VAA
Controller
PCB
Compressor
Type
Compressor model
Nominal output
Compressor oil ... Amount
Coil resistance (Ambient temp. 25°C)
Safety devices
Type
Overload relay
Operating temp.
Operating amp.(Ambient temp. 25°C)
Run capacitor
Crank case heater
Fan & Fan Motor
Type
Q'ty ... Dia.
Fan motor model ... Q'ty
No. of poles ... rpm (230 V, High)
Nominal output
Coil resistance (Ambient temp. 20°C)
Safety devices
Type
Operating temp.
Run capacitor
Heat Exch. Coil
Coil
Rows
Fin pitch
Face area
External Finish
W
cc
Open
°C
Close
°C
Trip in 6 to 16 sec. at 14A
µF
VAC
W
Open
°C
Close
°C
µF
VAC
mm
2
m
10
POW-C96GH
Rotary (Hermetic)
C-RN75H5A 80225245F
750
ROTARY OIL ... 470
C–R : 3.45
C–S : 8.79
External(OLR A)
MRA38082-3229
135±5
69±11
20
400
Propeller
1 ... ø370
K35610M01723 ... 1
6 ... 810
20
WHT-BRN : 341 - 392
WHT-PNK : 476 - 548
— —
Internal fuse
145±2
1.5
450
Aluminum plate fin / Copper tube
1
1.3
0.353
Acrylic baked-on enamel finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
External(OLR T)
CS-7C115
115±3
95±5

Advertisement

Table of Contents
loading

Table of Contents