Gree SAP09HP230V1AH Service Manual page 75

Hide thumbs Also See for SAP09HP230V1AH:
Table of Contents

Advertisement

Display Method of Indoor Unit
Indicator Display (during
Malfunction
blinking, ON 0.5s and OFF
Dual-8
NO.
Name
0.5s)
Code
Display
Operation
Indicator
Decrease
frequency
19
due to
F9
high air
discharge
Limit/
decrease
20
frequency
FH
due to
antifreezing
Voltage for
21
DC bus-bar
PH
is too high
Voltage of
22
DC bus-bar
PL
is too low
Compressor
Min
23
P0
frequence in
test state
Compresso r
rated
24
P1
frequenc e in
test state
Compressor
maximum
25
P2
frequence in
test state
72
Display Method of Outdoor
Indicator has 3 kinds of
display status and during
blinking, ON 0.5s and OFF
0.5s
Cool
Heating
Yellow
Red
Indicator
Indicator
Indicator
Indicator
OFF 1S
and
blink
twice
OFF 1S
and
blink
4 times
OFF 1S
and
blink
13 times
OFF 1S
and
blink
12 times
Unit
A/C status
Green
Indicator
All loads operate normally,
while
operation frequency for
compressor is decreased
All loads operate normally,
while operation frequency for
compressor is decreased
During cooling and drying
operation, compressor will stop
while indoor fan will operate;
During heating operation, the
complete unit will stop
operation.
During cooling and drying
operation, compressor will stop
while indoor fan will operate;
During heating operation, the
complete unit will stop
Service Manual
Possible Causes
Overload or temperature is too
high;
Malfunction of electric expansion
valve (EKV)
Poor air-return in indoor unit or fan
speed is too low
1. Measure the voltage of position
L and N on wiring board (XT), if the
voltage is higher than 265VAC, turn
on the unit after the supply voltage
is increased to the normal range.
2.If the AC input is normal,
measure the voltage of electrolytic
capacitor C on control panel (AP1),
if its normal, theres malfunction
for the circuit, please replace the
control panel (AP1)
1. Measure the voltage of position
L and N on wiring board (XT), if the
voltage is higher than 150VAC,
turn on the unit after the supply
voltage is increased to the normal
range.
2.If the AC input is normal,
measure the voltage of electrolytic
capacitor C on control panel (AP1),
if its normal, theres malfunction
for the circuit, please replace the
control panel (AP1)
Showing during min. cooling or
min. heating test
Showing during nominal cooling or
nominal heating test
Showing during max. cooling or
max. heating test
Installation and Maintenance