Appendix F: Non-Hitachi racks

All VSP Gx00 models storage systems can be installed into non-Hitachi racks.
The following describes the requirements and guidelines for installing the storage
system into a non-Hitachi rack.

Non-Hitachi rack support

The storage system supports non-Hitachi racks that meet Hitachi specifications.
Observe the following mounting guidelines for non-Hitachi racks:
The VSP Gx00 models support any 4-post, EIA-310-D compliant rack that has
adequate airflow and weight capacity.
PDUs must be mounted properly to avoid any issues while servicing the storage
system. The PDU receptacles must face toward the back (not toward each other). The
area behind the storage system and between the vertical 19-inch mounting posts
must be free of PDUs and cable loops.

Hitachi Universal V2 Rack rail kits

Use rail kits to mount the Hitachi Virtual Storage Platform family storage system in a
Hitachi Universal V2 Rack.
The following tables list the rail kit information for the specified storage systems.
Rail kit
Controller
DBS, DBL, and DBF drive
trays
DB60 dense intermix drive
tray
SVP server
Notes:
1. UNI: Universal rail kit A34V-600-850-UNI.
Hitachi Virtual Storage Platform G700 Hardware Reference Guide
Table 22 Rail kits for VSP Gx00 models
Hitachi Universal V2 Rack
1
UNI
2
CGR
Use the rail kit supplied with the DB60 dense intermix
drive tray.
Use the rail kit supplied with the SVP server.
Appendix F: Non-Hitachi racks
Third-party rack
1
UNI
1
UNI