Appendix E: Power Distribution Units For Hitachi Universal V2 Rack; Americas Single-Phase Pdu 1P30A-8C13-3C19Ul.p - Hitachi 88-02-0 Series Hardware Reference Manual

Virtual storage platform
Hide thumbs Also See for 88-02-0 Series:
Table of Contents

Advertisement

Appendix E: Power distribution units for Hitachi
Universal V2 Rack
The Hitachi Universal V2 Rack is equipped with specific power distribution units (PDU) for
Americas, APAC, and EMEA regions. The PDUs can provide electrical power to the storage
system in a single-phase or three-phase configuration.
Caution:
Before installing third-party devices into the rack, check the electrical
current draw of each device. Verify the electrical specifications and
allowable current load on each PDU before plugging the device into the
PDU.
Balance the electrical current load between available PDUs.

Americas single-phase PDU 1P30A-8C13-3C19UL.P

The following figure and table describes the specifications of the PDU.
Figure 1 Americas PDU for the Hitachi Universal V2 Rack (Single-phase PDU
1P30A-8C13-3C19UL.P)
Part Number
1P30A-8C13-3C19U
L.P

Appendix E: Power distribution units for Hitachi Universal V2 Rack

Hitachi Virtual Storage Platform G700 Hardware Reference Guide
Region
Americas
Single
Phase
Description
208V, 30A (24A
rated) 60Hz
8 IEC C13 + 3 IEC
C19 sockets
NEMA L6-30P
input power plug
4.5 m (14.76
feet) cable
101