Configuring Alarm Parameters - HIKVISION DS-2AE5232TI-A User Manual

Hd-tvi speed dome
Table of Contents

Advertisement

User Manual of HD-TVI Speed Dome
(3) Click IRIS+ again to confirm.
If you set the status as OPEN, alarm will be triggered by high electricity level; if you set
the status as CLOSE, alarm will be triggered by low electricity level; if you set the status as OFF,
it will be triggered when this input channel is shut off.
5. Configure the alarm linkage action.
You can specify the linked action when an alarm occurs.
(1) Move the cursor to LINKAGE and click the IRIS+ to enter edit mode.
(2) Click the up and down direction buttons to choose the desired linkage action. You can set
the alarm action as preset from 1 to 8, pattern from 1 to 5, patrol from 1 to 10, panning
scan, tilting scan, random scan, frame scan, panoramic scan, day mode, night mode or none.
You can also set the alarm output for the alarm. Please refer to Section 3.5.3 Configuring
Alarm Output for details.
6. Configure alarm priority.
Enter the PRIORITY menu and set the alarm priority as HIGH, MIDUEM or LOW.
If multiple alarms with different priorities are triggered at the same time, the dome only
responds to the alarm with the highest priority. If multiple alarms with the same priority are
triggered at the same time, then the dome will respond to each alarm according to the defined
alarm sequence.

3.5.2 Configuring Alarm Parameters

Purpose:
You can set the alarm related parameters following below instructions, including linkage action
interval, alarm duration and dome activity resumption.
Steps:
1. Enter the alarm parameter configuration menu:
MAIN MENUS > DOME SETTINGS > ALARM INPUT
2. Configure the interval of the alarm sequence.
When more than one alarm of the same priority occurs at the same time, the speed dome will
respond to one alarm first and then respond to the next one after the user-defined interval. You
can set the on SEQUENCE submenu from 1 to 200 seconds.
3. Configure the alarm rest delay.
If there's a linkage action has already been triggered by an alarm input, the speed dome will
only respond to the input from the same channel again after the user-defined reset delay time.
This is the rest time that the speed dome considers an alarm to be active when it's physically
cleared. You can set the DELAY TIME from 0 to 300 seconds.
4. Resume the dome activity.
You can set ALARM RESUME to ON to enable the speed dome to resume its previous activity
after the triggered actions finished.
 If the speed dome is moving when a linkage action is triggered, it will stop at the current
37

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ds-2ae5230t-a3Ds-2ae5123t-aDs-2ae7230ti-a

Table of Contents