Applications
4.5.5 Connecting a Releasing Device to the XLS-CM-N/
TC810N1013 Module
The module can control 1 A of current. Make sure to keep total system current within the limits of
the power supply. You can power the module from the power supply of the Control Panel or any
UL 864-listed 24 VDC regulated power-limited power supply for Fire Protective Signaling. For
more information, refer to the Device Compatibility Document.
+
Compatible UL-listed
24 VDC releasing device
Brown
+
REL-47K
(Use with Type Code
Rel Ckt ULC,
or see Circuit
Requirement 3.)
Note: See text for circuit requirements.
Compatible UL-listed
24 VDC releasing device
Brown
Note: See text for circuit requirements.
Figure 4.6 Typical Connection of a 24 VDC Releasing Device to XLS-CM-N/TC810N1013 Modules
Circuit Requirements. When connecting a releasing device to the XLS-CM-N/TC810N1013
module, note the following:
1.
Refer to the XLS140 Programming Manual for instructions on setting the Soak Timer.
2.
For applications using power-limited circuits:
a) Use an in-line supervisory device (P/N REL-47K) with the XLS-CM-N/TC810N1013
module. Connect the in-line supervisory device as shown in Figure 4.6.
b) Program the releasing circuit for Type Code REL CKT ULC.
c) Circuits are supervised against opens and shorts.
3.
For applications not requiring power-limited circuits:
a) in-line supervisory devices (P/N REL-47K) are not required; however, the releasing device
circuit is not supervised against shorts.
b) In non-power-limited applications, program the releasing circuit for Type Code
RELEASE CKT.
66
Red
N.C. Supervision
Relay Contact
Part of EOLR-1
+
Red
+
REL-47K
(Use with Type Code
Rel Ckt ULC,
N.C. Supervision
or see Circuit
Relay Contact
Requirement 3.)
Part of EOLR-1
XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005
9
0
7
8
9
6
10
5
11
4
8
1
12
3
13
2
1
14
0
15
7
2
TENS
8
7
9
6
5
6
3
4
3
2
1
5
4
0
ONES
LOOP
ADDRESS
XLS-CM-N
9
0
7
8
9
6
5
4
8
1
3
2
1
0
7
2
TENS
8
7
6
9
5
6
3
4
3
2
1
5
4
0
ONES
LOOP
ADDRESS
TC810N1013
Releasing Applications
SLC from FACP
or LEM-320
+
Non-resettable
24 VDC Power
+
Power Supervision
Relay (EOLR-1)
SLC from FACP
or LEM-320
-
+
Non-resettable
24 VDC Power
-
+
Power Supervision
Relay (EOLR-1)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents