System Cabinets - Honeywell XLS140 Installation Manual

Fire alarm control panel
Table of Contents

Advertisement

System Overview

2.3 System Cabinets

The control panel and modules are installed in a CAB-4 series backbox. There are four different
sizes available, holding from one to four rows of equipment plus batteries (up to two 25AH
batteries). Backboxes are ordered separately from doors. The doors can be mounted on the left or
the right side of the cabinet; reversible hinges are provided so that this choice can be made in the
field. Doors open a full 180 degrees and have locks. Mounting methods include surface-mounting
or semi-flush mounting on a wall between 16 inch (40.64 cm) on-center studs. A trim ring option is
available for semi-flush mounting.
External measurements for each backbox are provided below; door dimensions are larger. Refer to
CAB-3/CAB-4 Series Cabinet Installation Document (shipped with the cabinet) for specific
mounting drawings and door dimensions.
A-size backbox
(one row)
B-size backbox
(two rows)
C-size backbox
(three rows)
D-size backbox
(four rows)
Trim Rings: When using trim rings, mount backbox with at least 1 inch (2.54 cm) between wall surface and
front of backbox, to allow door to open fully past the trim ring.
The control panel and adjacent first-row modules mount in chassis CHS-M2, typically in the
first/top row of the backbox. Additional rows of modules can be mounted in chassis CHS-4N
and/or CHS-4L.
NOTE: If using the new CHS-M2 in a CAB-3 series backbox or in a CAB-4 series backbox
manufactured before October 2002, verify stud height and cut any stud that exceeds 0.375 in.
(9.525 mm) if a CPU is being mounted above it. See warning and instructions in Section 3.5.1
"Control Panel Circuit Board & Keypad/Display Unit".
Some additional components available in the CAB-4 series include:
DP-DISP An Inner Dress Panel for covering the backbox area surrounding display panels and
various modules (required for Canadian installations).
NOTE: For use with XLS-NCA, KDM-2, and primary displays.
BMP-1 Blank Module Plate for covering an unused dress-panel position. Provides another option
for mounting modules such as TM-4, NCM-W, or NCM-F.
BP-4 Battery dress panel
18
24.00 in (60.96 cm) wide
20.00 in (50.8 cm) tall
5.218 in (13.254 cm) deep
Uses optional trim ring TR-A4
24.00 in (60.96 cm) wide
28.5 in (72.39 cm) tall
5.218 in (13.254 cm) deep
Uses optional trim ring TR-B4
24.00 in (60.96 cm) wide
37.125 in (94.297 cm) tall
5.218 in (13.254 cm) deep
Uses optional trim ring TR-C4
24.00 in (60.96 cm) wide
45.75 in (1162.05 cm) tall
5.218 in (13.254 cm) deep
Uses optional trim ring TR-D4
XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005
System Cabinets
Optional trim ring TR-A4
Opening: 24.062 in (61.118 cm) wide;
20.062 in (50.881 cm) tall.
Molding width: 1.375 in (3.493 cm)
Optional trim ring TR-B4
Opening: 24.062 in (61.118 cm) wide;
28.562 in (72.548 cm) tall.
Molding width: 1.375 in (3.493 cm)
Optional trim ring TR-C4
Opening: 24.062 in (61.118 cm) wide;
37.187 in (94.455 cm) tall.
Molding width: 1.375 in (3.493 cm)
Optional trim ring TR-D4
Opening: 24.062 in (61.118 cm) wide;
45.812 in (114.775 cm) tall.
Molding width: 1.375 in (3.493 cm)

Hide quick links:

Advertisement

Table of Contents
loading