MODULE
SPECIFICATIONS
PC4108 Expansion Module
• Up to 128 zones total on system
• 8 zone expansion module
• Normally closed loops, EOL resistor, Double EOL
resistor support
• Four wire (QUAD) hook-up to COMBUS
• Nominal current draw of 25 mA
• Provides Tamper Reporting Codes
• Low COMBUS supervision to PC4020 Main Board
PC4116 Expansion Module
• Up to 128 zones in total on system
• Normally closed loops, EOL resistor, Double EOL
resistor support
• 16 zone expansion module
• Four wire (QUAD) hook-up to COMBUS
• Nominal current draw of 30 mA
• Provides Tamper Reporting Codes
• Low COMBUS supervision to PC4020 Main Board
PC4204 High Current Output Module
• 4 output high current module
• Up to 16 modules on system
• Minimum 40 VA 16-18 volt transformer required
• Minimum 4 Amp-Hour, 12 volt battery required
• Each output programmable for 1 of 35 options
• Four wire (QUAD) hook-up to COMBUS
• Nominal current draw of 25 mA
• Provides Tamper and Trouble Reporting Codes
• Low COMBUS supervision to PC4020 Main Board
• 1.5 Amp output
PC4216 Low Current Output Module
• 16 output low current module
• Up to 9 modules on system
• All module programmable for all 16 outputs, 1 of 35
options for each
• 8 modules programmable as alarm annunciators or
zone followers
• Four wire (QUAD) hook-up to COMBUS
• Nominal current draw of 35 mA
• Provides Tamper Reporting Codes
• Low COMBUS supervision to PC4020 Main Board
PC4400 RS-232 Interface Adapter
Module
• True RS-232 technology
• Handshake software switches
• Protocol XON/XOFF or DTR
• 4 possible baud rates 300, 600, 1200 and 2400
• Four wire (QUAD) hook-up to COMBUS
• Nominal current draw of 35 mA
• Provides Tamper Reporting Codes
• Low COMBUS supervision to PC4020 Main Board
PC4700 Fire Module
• One module per system
• 2 wire Class B/Style B smoke detector circuit (20
detectors maximum)
• 4 wire Class D/ Style D waterflow circuit (5 sensor
maximum [NFPA 3-8-6-3])
• 1 fully programmable supervised bell output.
(Controlled via the Main Bell Output)
• Dual supervised Telco lines - With the ability to switch to
the second line in the event of a line failure.
• Ground fault detection
• Nominal current draw of 35mA
• Four wire quad connection to Combus
• Low Combus supervision to the Main Board
• Reporting codes for:
- Bell CCT Trouble
- Waterflow Alarm/Trouble
- 2 Wire smoke Alarm/Trouble
- TLM trouble/restoral for line 1 and line 2
- Ground Fault
LCD4500 Remote Keypad
• Up to 16 keypads on system
• Alphanumeric liquid crystal display
• Built-in piezoelectric buzzer
• Full annunciation of zones and system status
• Four wire (QUAD) hook-up to COMBUS
• Nominal current draw of 25 mA (maximum 55 mA)
• Provides Tamper Reporting Codes
• Low COMBUS supervision to PC4020 Main Board
• Dimensions 5.75" x 4.5" x 1" deep (144 x 114 x 25 mm)
LCD4520 Remote Keypad
• Up to 16 keypads on system
• Alphanumeric liquid crystal display
• Built-in piezoelectric buzzer
• Full annunciation of zones and system status
• Four wire (QUAD) hook-up to COMBUS
• Nominal current draw of 25 mA (maximum 55 mA)
• Provides Tamper Reporting Codes
• Low COMBUS supervision to PC4020 Main Board
• Dimensions 5.75" x 4.5" x 1" deep (144 x 114 x 25 mm)
• Loss of COMBUS communication supervision
• Required for PC4020CF
8