Daikin Altherma 3 H HT F Installer's Reference Manual page 89

Hide thumbs Also See for Altherma 3 H HT F:
Table of Contents

Advertisement

EPRA14~18D + ETVH16SU18+23E
Daikin Altherma 3 H HT F
4P644738-1A – 2022.03
c
c
c
a Individual room thermostat (optional)
b Overpressure bypass valve (delivered as accessory)
c Shut-off valve
Maximum water volume
NOTICE
The maximum water volume depends on whether glycol is added to the water
circuit. For more information on the addition of glycol, refer to
water circuit against
Use the following graph to determine the maximum water volume for the
calculated pre-pressure.
A
2,4
2,1
1,8
1,5
1,2
1
0,9
0,6
0,3
20
70
A Pre-pressure (bar)
B Maximum water volume (l)
Water
Water + glycol
Example: Maximum water volume and expansion vessel pre-pressure
Installation
height
(a)
difference
≤7 m
No pre-pressure adjustment is
required.
c
c
M1
M2
a
a
a
4
freezing" [
 98].
120
220
140
175
200
Water volume
≤190 l
Do the following:
8
Piping installation
|
b
M3
"8.2.7 To protect the
270
255
B
>190 l
Decrease the pre-pressure
according to the required
installation
difference. The pre-pressure
should decrease by 0.1 bar
for each metre below 7 m.
Check if the water volume
does
NOT
exceed
maximum
allowed
volume.
Installer reference guide
height
the
water
89