Daikin Altherma 3 H HT F Installer's Reference Manual page 205

Hide thumbs Also See for Altherma 3 H HT F:
Table of Contents

Advertisement

Emergency
EPRA14~18D + ETVH16SU18+23E
Daikin Altherma 3 H HT F
4P644738-1A – 2022.03
INFORMATION
When heating of the DHW by the heat pump is too slow, it may affect a comfortable
operation of the space heating/cooling circuit. If so, allow the backup heater to assist
during DHW operation by setting [4-00]=1 or 2.
INFORMATION
Only for systems with integrated domestic hot water tank: If backup heater
operation during space heating needs to be limited but can be allowed for domestic
hot water operation, then set [4‑00] to 2.
Emergency
When the heat pump fails to operate, the backup heater can serve as an
emergency heater. It then takes over the heat load either automatically or by
manual interaction.
When Emergency is set to Automatic and a heat pump failure occurs, the
backup heater automatically takes over the domestic hot water production and
space heating.
When Emergency is set to Manual and a heat pump failure occurs, the
domestic hot water heating and space heating stops.
To manually recover it via the user interface, go to the Malfunctioning main
menu screen and confirm whether the backup heater can take over the heat load
or not.
Alternatively, when Emergency is set to:
-
auto SH reduced/DHW on, space heating is reduced but domestic hot
water is still available.
-
auto SH reduced/DHW off, space heating is reduced and domestic hot
water is NOT available.
-
auto
SH
normal/DHW
domestic hot water is NOT available.
Similarly as in Manual mode, the unit can take the full load with the backup
heater if the user activates this via the Malfunctioning main menu screen.
To keep energy consumption low, we recommend to set Emergency to auto SH
reduced/DHW off if the house is unattended for longer periods.
#
Code
[9.5.1]
[4-06]
INFORMATION
The auto emergency setting can be set in the menu structure of the user interface
only.
off, space heating operates as normally but
Description
0: Manual
1: Automatic
2: auto SH reduced/DHW on
3: auto SH reduced/DHW off
4: auto SH normal/DHW off
10
Configuration
|
Installer reference guide
205