Daikin Altherma 3 H HT F Installer's Reference Manual page 176

Hide thumbs Also See for Altherma 3 H HT F:
Table of Contents

Advertisement

10
|
Configuration
Installer reference guide
176
Emitter type
Additional zone
0: Underfloor
heating
1: Fancoil unit
2: Radiator
Setpoint range
For more information about Setpoint range, see
#
Code
Leaving water temperature range for the additional leaving water temperature
zone (= the leaving water temperature zone with the highest leaving water
temperature in heating operation and the lowest leaving water temperature in
cooling operation)
[3.8.1]
[9-05]
[3.8.2]
[9-06]
[3.8.3]
[9-07]
[3.8.4]
[9-08]
Control
The control type for the additional zone is read only. It is determined by the control
type of the main zone.
See
"10.5.3 Main
zone" [
#
Code
[3.9]
N/A
Ext thermostat type
Only applicable in external room thermostat control.
Also see
"10.5.3 Main
zone" [
Space heating setpoint
range [9‑05]~[9‑06]
Maximum 55°C
Maximum 55°C
Maximum 70°C
Heating minimum: 15°C~37°C
Heating maximum
[2‑0D]=2 (emitter type additional zone =
radiator)
37°C~68°C
Else: 37°C~55°C
Cooling minimum
5°C~18°C
Cooling maximum
18°C~22°C
4
 162].
Control:
Leaving
main zone is Leaving water.
External room thermostat if the control
type of the main zone is:
-
External room thermostat,or
-
Room thermostat.
4
 162].
Target delta T in heating
[1‑0C]
Variable (see [3.B.1])
Variable (see [3.B.1])
Fixed 10°C
"10.5.3 Main
zone" [
Description
Description
water if the control type of the
EPRA14~18D + ETVH16SU18+23E
Daikin Altherma 3 H HT F
4P644738-1A – 2022.03