Daikin Altherma 3 H HT F
4P644738-1A – 2022.03
Item
Heat pump convector
Remote outdoor sensor
Remote indoor sensor
9
Electrical installation
|
Description
There are different controllers and setups
possible for the heat pump convectors.
Depending on the setup, you also need to
implement a relay (field supply, see
addendum book for optional equipment).
For more information, see:
Installation manual of the heat pump
convectors
Installation manual of the heat pump
convector options
Addendum book for optional equipment
Wires: 0.75 mm²
Maximum running current: 100 mA
For the main zone:
[2.9] Control
[2.A] Ext thermostat type
For the additional zone:
[3.A] Ext thermostat type
[3.9] (read-only) Control
See:
Installation manual of the remote outdoor
sensor
Addendum book for optional equipment
Wires: 2×0.75 mm²
[9.B.1]=1 (External sensor = Outdoor)
[9.B.2] Ext. amb. sensor offset
[9.B.3] Averaging time
See:
Installation manual of the remote indoor
sensor
Addendum book for optional equipment
Wires: 2×0.75 mm²
[9.B.1]=2 (External sensor = Room)
[1.7] Room sensor offset
Installer reference guide
117