Daikin Altherma 3 H HT F Installer's Reference Manual page 215

Hide thumbs Also See for Altherma 3 H HT F:
Table of Contents

Advertisement

Sensors
EPRA14~18D + ETVH16SU18+23E
Daikin Altherma 3 H HT F
4P644738-1A – 2022.03
#
Code
[9.A.1]
[D‑08]
[9.A.2]
[D‑09]
External sensor
#
Code
[9.B.1]
[C–08]
Ext. amb. sensor offset
ONLY applicable in case an external outdoor ambient sensor is connected and
configured.
Description
Electricity meter 1:
0 None: NOT installed
1 1/10kWh: Installed
2 1/kWh: Installed
3 10/kWh: Installed
4 100/kWh: Installed
5 1000/kWh: Installed
Electricity meter 2:
0 None: NOT installed
1 1/10kWh: Installed
2 1/kWh: Installed
3 10/kWh: Installed
4 100/kWh: Installed
5 1000/kWh: Installed
In case of pulse meter for photovoltaic panels:
6 100/kWh for PV panel: Installed
7 1000/kWh for PV panel: Installed
Description
External sensor: When an optional external
ambient sensor is connected, the type of the
sensor must be set.
0 None : NOT installed. The thermistor in the
dedicated Human Comfort Interface and in the
outdoor unit are used for measurement.
1 Outdoor: Connected to PCB of the indoor
unit measuring the outdoor temperature.
Remark:
For
some
temperature sensor in the outdoor unit is still
used.
2 Room: Connected to PCB of the indoor unit
measuring the indoor temperature. The
temperature sensor in the dedicated Human
Comfort Interface is NOT used anymore.
Remark: This value has only meaning in room
thermostat control.
10
Configuration
|
functionality,
the
Installer reference guide
215