Daikin Altherma 3 H HT F Installer's Reference Manual page 289

Hide thumbs Also See for Altherma 3 H HT F:
Table of Contents

Advertisement

Field settings table
Breadcrumb Field code
Setting name
9.1.3.3
[E-05]
Domestic hot water
[E-06]
[E-07]
9.1.3.4
[4-06]
Emergency
9.1.3.5
[7-02]
Number of zones
9.1.3.6
[E-0D]
Glycol Filled system
9.1.3.7
[6-02]
BSH capacity (*3)
9.1.3.8
[C-02]
Bivalent
└─ Backup heater
9.1.4.1
[5-0D]
Voltage
9.1.4.2
[4-0A]
Configuration
9.1.4.3
[6-03]
Capacity step 1
9.1.4.4
[6-04]
Additional capacity step 2
└─ Main zone
9.1.5.1
[2-0C]
Emitter type
9.1.5.2
[C-07]
Control
9.1.5.3
Setpoint mode
9.1.5.4
Schedule
9.1.5.5
WD curve type
9.1.6
[1-00]
Low ambient temp. for LWT main zone heating WD curve.
9.1.6
[1-01]
High ambient temp. for LWT main zone heating WD curve.
9.1.6
[1-02]
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
9.1.6
[1-03]
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
9.1.7
[1-06]
Low ambient temp. for LWT main zone cooling WD curve.
9.1.7
[1-07]
High ambient temp. for LWT main zone cooling WD curve.
9.1.7
[1-08]
Leaving water value for low ambient temp. for LWT main zone cooling WD curve.
9.1.7
[1-09]
Leaving water value for high ambient temp. for LWT main zone cooling WD curve.
└─ Additional zone
9.1.8.1
[2-0D]
Emitter type
9.1.8.3
Setpoint mode
9.1.8.4
Schedule
9.1.9
[0-00]
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
9.1.9
[0-01]
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
9.1.9
[0-02]
High ambient temp. for LWT add zone heating WD curve.
9.1.9
[0-03]
Low ambient temp. for LWT add zone heating WD curve.
(*1) *6V*_(*2) *9W*_
(*3) ETB*_(*4) ETV*_
(*5) *X*_(*6) *H*_(*7) *SU*_
(*8) E_(*9) E7
Range, step
Default value
R/W
No DHW (*3)
EKHW, small volume (*3)
Integrated (*4)
EKHW, big volume (*3)
EKHWP (*3)
3rd party, small coil (*3)
3rd party, big coil (*3)
R/W
0: Manual
1: Automatic
2: Auto red SH/ DHW ON
3: Auto red SH/ DHW OFF
4: Auto normal SH/ DHW OFF
R/W
0: Single zone
1: Dual zone
R/W
0: No
1: Yes
R/W
0~10kW, step: 0,2kW
3kW (*3)
0kW (*4)
R/W
0: No
1: Bivalent
R/W (*1)
0: 230V, 1~ (*1)
R/O (*2)
1: 230V, 3~ (*1)
2: 400V, 3~ (*2)
R/W
0: 1
1: 1/1+2 (*1) (*2)
2: 1/2
3: 1/2 + 1/1+2 in emergency
R/W
0~10kW, step: 0,2kW
2kW (*1)
3kW (*2)
R/W
0~10kW, step: 0,2kW
4kW (*1)
6kW (*2)
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
R/W
0: LWT control
1: Ext RT control
2: RT control
R/W
0: Fixed
1: WD heating, fixed cooling
2: Weather dependent
R/W
0: No
1: Yes
R/W
0: 2-points
1: Slope-Offset
R/W
-40~5°C, step: 1°C
-15°C
R/W
10~25°C, step: 1°C
15°C
R/W
[9-01]~[9-00], step: 1°C
[2-0C]=0
35°C
[2-0C]=1
45°C
[2-0C]=2
65°C
R/W
[9-01]~min(45, [9-00])°C , step: 1°C
[2-0C]=0
25°C
[2-0C]=1
35°C
[2-0C]=2
35°C
R/W
10~25°C, step: 1°C
20°C
R/W
25~43°C, step: 1°C
35°C
R/W
[9-03]~[9-02]°C, step: 1°C
22°C
R/W
[9-03]~[9-02]°C, step: 1°C
[2-0C]=0
18°C
[2-0C]=1
7°C
[2-0C]=2
18°C
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
R/W
0: Fixed
1: WD heating, fixed cooling
2: Weather dependent
R/W
0: No
1: Yes
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
35°C
R/W
[9-05]~[9-06]°C, step: 1°C
65°C
R/W
10~25°C, step: 1°C
15°C
R/W
-40~5°C, step: 1°C
-15°C
5/13
Installer setting at variance with
default value
Date
Value
4P644734-1A - 2022.03