6.3.1
Performing high-voltage testing
If high-voltage testing of the control cabinet or the power
supply as a stand-alone component is planned during final
inspection and testing, the following features must be
observed.
The power supply wiring must be implemented as
shown in the wiring diagram.
The maximum permissible test voltages must not be
exceeded.
Avoid unnecessary loading or damage to the power supply
due to excessive test voltages.
For the relevant applicable test voltages and
insulation distances, refer to the corresponding
table (see technical data: electric strength of the
insulation section).
Figure 1
Potential-related wiring for the high-voltage
test
2
3.1 2.1 2.2
+
SIG
Output DC
U
Out
Signal (SIG)
P
> P
Out
Thr
Boost >100%
> 75%
> 50%
DC OK
Input DC
+
1.1 1.2
Key
No. Designation
1
DC output circuit Blue
2
Signal contacts Blue
3
High-voltage
tester
4
DC input circuit Red
110257_en_00
1
HV
3
/=
4
Color coding
Potential lev-
els
Potential 1
Potential 1
--
--
Potential 2
QUINT4-PS/12-24DC/24DC/1.3/SC
PHOENIX CONTACT
16/32