Phoenix Contact QUINT4-PS/12-24DC/24DC/1.3/SC Manual page 11

Dc/dc converter
Table of Contents

Advertisement

Immunity according to EN 61000-6-1 (residential), EN 61000-6-2 (industrial), and EN 61000-6-5 (power station
equipment zone), IEC/EN 61850-3 (energy supply)
CE basic standard
Surge voltage load (surge) EN 61000-4-5
Conducted interference EN 61000-4-6
Power frequency magnetic field EN 61000-4-8
110257_en_00
(immunity for industrial
Input
Output
Signal
Comments
Input/Output/Signal
Frequency range
Voltage
Comments
50 Hz , 60 Hz ( 30 A/m )
Comments
QUINT4-PS/12-24DC/24DC/1.3/SC
Minimum normative
requirements of
EN 61000-6-2 (CE)
environments)
0.5 kV (Test Level 3 -
symmetrical)
1 kV (Test Level 3 -
asymmetrical)
0.5 kV (Test Level 2 -
symmetrical)
1 kV (Test Level 1 -
asymmetrical)
0.5 kV (Test Level 2 -
symmetrical)
1 kV (Test Level 1 -
asymmetrical)
Criterion B
asymmetrical
0.15 MHz ... 80 MHz
10 V (Test Level 3)
Criterion A
not required
not required
Criterion A
Higher requirements in
practice (covered)
1 kV (Test Level 4 -
symmetrical)
2 kV (Test Level 4 -
asymmetrical)
1 kV (Test Level 3 -
symmetrical)
2 kV (Test Level 3 -
asymmetrical)
1 kV (Test Level 4 -
symmetrical)
2 kV (Test Level 4 -
asymmetrical)
Criterion A
asymmetrical
0.15 MHz ... 80 MHz
10 V (Test Level 3)
Criterion A
16.67 Hz , 50 Hz , 60 Hz
( 100 A/m 60 s )
50 Hz , 60 Hz ( 1 kA/m , 3 s )
0 Hz ( 300 A/m , DC, 60 s )
Criterion A
PHOENIX CONTACT