Technical data
Introduction
Technical data for the AC-M5 W MKII unit.
Performance
The air conditioner has a maximum cooling capacity of 4.7 kW.
characteristics
When the relative humidity of the air inlet is high, the air can be cooled below its dew
point and thus condense some of the water vapour to free water. This requires a certain
amount of latent cooling but provides a dehumidification process, which is an important
factor in comfortable air supply conditions.
The operating range is between 20 and 60 °C approximately and is controlled by the
HP-pressure switch. In relatively dry locations the air temperature drop will depend on
inlet conditions.
Data
Data and dimensions on the cabinet are shown in the following table:
Voltage/PH/frequency
Electric consumption, max.
Cooling capacity, max.
Heating capacity (option)
Airflow low, evaporator
Airflow high, evaporator
Airflow, condenser
Refrigerant/Load
Max. refrigerant pressure
Operation temp. range
Weight
Noise level (1 m) low speed
Noise level (1 m) high speed
*)
With/without compressor active
Specification
Value
230 V 1 PH/50 Hz
2.4 kW/11.2 A
4.7 kW
2.0 kW/8.6 A
420 m³/h
900 m³/h
1475 m³/h
R134a/1.4 kg
28 Bar
20-60 °C
79 kg
*)
49/48
dB(A)
*)
64/63.5
dB(A)
37