Preventive maintenance,
Monthly preven-
Please follow this procedure to do monthly preventive maintenance or every 200 hours
tive maintenance
of operation:
Caution
When dismounting the front cover you are breaking the EMC seal. When remounting
the unit be aware that the EMC seal is intact and restored properly.
Step
continued
1
Perform daily maintenance
2
Clean the air filter with a hoover or wash it in luke warm soap water.
See the drawing below and follow the steps to get access to the filter
3
Loosen the two latches in each side of the unit
4
Grab the handles
5
Fasten the screws
6
Dismount the front frame by unscrewing 16 torx 21 screws
the filter
7
Grap the filter
behind the frame and clean it with a hoover or wash in luke
warm soap water
8
Check that the condensate drain is not blocked. Use
high pressure air from the outside of the unit for
5 seconds to remove dirt.
Condensate drain pipe
9
Follow the above steps just in reverse order to remount the unit
Make sure that the filters are dry before they return to service again and are
subjected to dust
Action
(one in each side) and pull the unit into the container
(one in each side) to fix the unit
to get access to
Continued overleaf