Automatic dosing and bleed control package
Table of Contents

Advertisement

Possible cause
Improper wiring of valve or controller
Conductivity rose over alarm limit while biocide lockout
occured
Clogged bleed line
Faulty bleed relay
Low or Low-Low Alarm
Occurs if the conductivity drops below the low conductivity alarm set points. If your unit is programmed for an
alarm relay output, the relay alarm will activate. The controller will continue to check the conductivity, and any
outputs using the conductivity well remain active.
Possible cause
Sensor disconnected
Sensor dry
Pre-bleed set too low
Bleed valve stuck open
Faulty electrode
Improper wiring of electrode
Faulty bleed relay
Output Timeout
This error condition will stop control. It is caused by the output (either relay of analog) being activated for longer
than the programmed time limit.
Possible cause
Programmed value too low for normal
conditions
Bleed flow rate too low
Bleed valve not opening
Sensor not responding
6 Operating Conditions
6 Operating Conditions
Corrective action
Correct wiring
Allow normal bleed to occur
Clean
Replace
Corrective action
Reconnect. Check cable for continuity.
Check tee for obstruction. Verify flow.
Change location of electrode.
Check pre-bleed setting
Repair or replace bleed valve
Replace sensor
Correct wiring
Replace relay
Corrective action
Increase time limit
Check for clogged strainer. Check for insufficient pressure
differential.
Check for faulty bleed valve. Check bleed valve wiring. Check
controller relay.
Clean sensor, check wiring, replace sensor.
W W W . B A L T I M O R E A I R C O I L . E U
35