BAC BCP2D Installation, Operating, Maintenance page 30

Automatic dosing and bleed control package
Table of Contents

Advertisement

FILE UTILITIES
Allows you to export event logs to a USB stick, export the configuration and settings (for later back-up or
program additional controllers in the same way).
File Transfer
Displays the status of the last attempt to export a file.
Status
Export Event Log
Save the event log file to a USB stick. This records set point changes, user calibrations,
alarms, relay state changes, file exports, etc.
Export System
Save the system log file to a USB stick. This records hardware changes, software
Log
upgrades, automatic calibrations, power loss, system-level issues, etc.
Import User
Remove power from the controller and insert a USB stick that contains the settings that
Config File
you want to import to this controller (see Export User Config File below). Press the
Enter key and then press the Confirm key to transfer those settings to this controller.
Export User
The user configuration file contains all settings for the controller. Enter this menu to
Config File
save the controller's settings to a USB stick for using later to restore settings to this
controller, or to program additional controllers with the same settings as this one. It
takes several minutes to create the file and transfer it to the stick. Remove power from
the controller and insert a USB stick. Press the Enter key and then press the Confirm
key to transfer a file containing the controller's settings to the USB stick.
Restore Default
Enter this menu to restore all of the settings to the factory default values. Any changes
Config
to settings that were previously made will be lost!
Software
Remove power from the controller and insert a USB stick that has the upgrade file
Upgrade
stored in the root directory into the USB connector. Press the Enter key, and then press
the Confirm key to start the upgrade.
Remove power before inserting or removing the USB stick.
NORMAL STARTUP
Startup is a simple process once your set points are in memory.
Fill the drums with the appropriate chemicals
Turn on the controller, calibrate the sensor if necessary (normally not required)
Prime the dosing pumps
-
Select Output Menu
-
Select Bio R2
-
Select Utilities
-
Select HOA Menu and switch to "Hand" mode
30