Use the left/right and Higher/Lower arrow key to change value if required (default 1 liter / impulse)
Press the Confirm key to accept the change
Water meter
Outputs R1, R2 and R3
R1: Bleed valve
Preprogrammed with default values by BAC, see "Default parameters and set points" on page 16
Enter the correct bleed set point with following procedure:
Program the setting for each output
The Bleed R1 relay output will be highlighted
Press the Settings key
Press the scroll down key until the Setpoint is highlighted
Press the Enter key
Use the left/right Higher/Lower arrow key to change value if required (default is 1200)
Press the Confirm key to accept the change
R2: Bio Timer
Preprogrammed with default values by BAC, see "Default parameters and set points" on page 16
Enter the correct values with following procedures:
The Bio Timer R2 relay output will be highlighted
26