BAC BCP2D Installation, Operating, Maintenance page 29

Automatic dosing and bleed control package
Table of Contents

Advertisement

Press the Enter key
Use the Higher/Lower arrow key to change the duration (Hours/Minutes/Seconds)
Validate
Press the scroll down key until the "Accum Volume" is highlighted (Default is 200 liters)
Use the Higher/Lower arrow key to change the duration (Hours/Minutes/Seconds)
Validate
ANALOG OUTPUT 4 - 20 MA (OPTIONAL EXECUTION WHEN ORDERED)
This option will allow you to get the output value for the conductivity (S1).
Press the Settings key view of change the settings related to the analog output.
4 mA Value
20 mA Value
6 Operating Conditions
6 Operating Conditions
Enter the value of the conductivity to correspond to 4 mA output signal (default 0
MicroSiemens)
Enter the value of the conductivity to correspond to 20 mA output signal (default
3600 MicroSiemens)