CONTROLLER SETTINGS

Default parameters and set points

The BACT 100 controller has been preprogrammed specifically for use with BAC evaporative cooling
equipment.
MENU INPUT
S1 - Conductivity
LoLo Alarm (Very low alarm)
Low Alarm
High Alarm
HiHi Alarm (Very high alarm)
Deadband
Alarm suppression
Reset Calibration values
Cal Req'd Alarm
Smoothing factor
Cell Const
Cable length
Gauge
Default temp
Temp Comp
Units
Name (change with language, default is English)
Type
16
W W W . B A L T I M O R E A I R C O I L . E U
200 µS/cm
200 µS/cm
3500 µS/cm
3500 µS/cm
25 µS/cm
none
365 days
0 %
1,000 1/cm
6,10 m
22 awg/0,35mm²
25 °C
NaCl
µS/cm
Conduct
Contacting Cond
5 Controller Settings
5 Controller Settings