ZC1-8B Connections and Ratings
4 - 122
Technical Manuals Online! - http://www.tech-man.com

Electrical connections:

firealarmresources.com
SPEAKER ZONE DECIBEL LOSS
for 25.2V RMS, 35W load
Gauge
Length
14 AWG
16 AWG
(feet)
(loss in decibels)
200
0.2
0.3
400
0.5
0.7
600
0.7
1.1
800
0.9
1.5
1000
1.2
1.8
SPEAKER ZONE DECIBEL LOSS
for 70.7V RMS, 25W load
Gauge
Length
16 AWG
(feet)
(loss in decibels)
200
0.04
400
0.07
600
0.11
800
0.14
1000
0.18
18 AWG
0.6
1.1
1.6
2.2
2.7
18 AWG
0.06
0.11
0.17
0.22
0.27