Siemens Cerberus PYROTRONICS MXL Operation, Installation, And Maintenance Manual page 180

Table of Contents

Advertisement

CRM-4 Connections and Ratings
Electrical ratings:
24 VDC
15mA (no energized relays)
Add: 18.7mA per energized relay
(75mA - all relays energized)
Technical Manuals Online! - http://www.tech-man.com
CRM-4 Relay Wiring
firealarmresources.com
MOM-4
(TB-1, TB-2, TB-3, or TB-4)
or
MOM-2
(TB2 or TB4)
NOTES
1. Contact rating: 2A,
30VDC/120 VAC
resistive.
2. Use only with power
limited / Class 2
circuits.
3. Coils are supervised
when de-energized.
4. Contacts are not
supervised.
5. All relay contacts are
shown in normal
(de-energized) state.
4 - 13