Siemens SINAMICS MV 9LD4110-7EX70-1AA0 Operating Instructions Manual page 86

Table of Contents

Advertisement

Electrical connection
6.1 Safety instructions for electrical connection
Danger due to defective seals
When working on the device, seals at the doors, roof panels as well as front, rear and side panels
can be damaged. Operation with defective seals can result in death, serious injury or material
damage.
• Replace the defective seals before commissioning.
• Observe the environmental conditions stated in the technical data.
Injury caused by short circuit
Damaged cables, or their improper routing, can cause damage to property and personal injury.
• Only use cables that are completely intact and not damaged. Correctly route the cables. Do
not interchange input and output terminals.
• Make sure that a short-circuit cannot occur on the power cables due to failure of the
insulation as a result of incorrect cable installation.
• Check the electrical connections after service work.
Danger caused by incorrect cable routing
Arcing can occur if cables are not routed in the supplied cable channels. This can result in death,
serious injuries or material damage.
• Use the cable ducts and cable entries on the roof to route the cables when electrically
connecting the cabinets.
Material damage caused by parts that can be magnetized
The use of magnetizable parts, e.g. ferrous cable clamps, is not permitted. Using parts and
components that can be magnetized can cause damage.
• Only use parts that consist of non-magnetic material.
Cable fire caused by high transition resistances
Cables connected to the connection point that are not in compliance with the applicable
regulations represent a high electrical transition resistance that can cause thermal damage
(fire) during operation.
• Tighten the screws with the required torque.
Damage caused by incorrectly shrinking cable terminations
If you are connecting the mains and motor-side power cables, when shrinking the cable
terminations, other control lines and fiber-optic cables in the surrounding cable channels can
become damaged.
• When shrinking, ensure not to damage cables in the surrounding cable channels.
84
3rd Party LCI Control Upgrade
Operating Instructions, 02/2022, A5E31872818

Advertisement

Table of Contents
loading

Table of Contents