M a n u a l of d e h u m i d i f i e r DanVex DEH-3K DanVex DEH-5K DanVex DEH-10K Industrial Condensing Dehumidifiers DEH-3K DEH-5K DEH-10K ■ Please read the manual carefully and in full before using the unit.
Page 2
Copying of this manual, or part of it, is forbidden without prior written permission from DANVEX.The warranty and technical shock or fire. support of this product are only valid in the country or region of purchase.
TABLE OF CONTENTS (5.2.1)Duct Check 1. General (5.2.2)Wiring Check 1.1 Application (5.2.3)Controller Check 1.2 Content 5.3 Unit Running 2. Unit 5.4 Air rate Adjustment 2.1 Introduction 5.5 Performance Test 2.2 Working Principle 6. Controller 2.3 Performance Cur ve 6.1 General 2.4 Airflow Direction (6.1.1)Controller Terminals 2.5 Housing &...
1. General 2. Unit 1.1 Application 2.1 Introduction The design of the dehumidifier meets the requirements of the IEC protection level IP 45. Cabinet-type dehumidification equipment adopts direct evaporative cooling design, which can dr y the air 2.2 Working Principle under atmospheric pressure.
2.3 Performance Cur ve DEH-3K-capacity cur ve 2.4 Airflow Direction Dr y Air DANVEX Dehumidifier is designed to achieve optimum result in terms of Airflow, Dehumidify Capacity, Energy Efficiency and Air Distribution for better and more even coverage area. DEH-5K-capacity cur ve...
High-temperature protection: The unit is designed with high-temperature protection to prevent the compressor from burning under continuous operation at high temperature. § Low-pressure protection: Prevent the compressor from burning out due to continuous operation without DEH-3K/5K refrigerant in the system.
3. Installation 3.1 Introduction 3.7 Duct Connection If the air outlet is connected to a duct, the size of the treated air duct should comply with the The cabinet type dehumidifier can be installed in many places, depending on the needs of the owner. If recommended value of ISO7807.
Correctly designed condensate trap (below) § § Avoid placing the humidity probe near heat sinks or exposed to direct sunlight, because temperature Condensate system under normal operating conditions: changes will affect Actual detection value. 1. Level A reflects the negative static pressure. §...
4. Ducting 4.1 Introduction There are many ways to install dehumidifiers, including non-ducted installation, ducting for fresh Air, installation with HVAC system,etc. Please read the manual carefully and consult relevant technicians and experts before installation. 4.1.1 Independent operation of dehumidifier Put the dehumidifier in the room independently, so that the humidity in the room will drop quickly, without connecting the pipes.
5. Commitioning 5.2.3 Controller Check 5.1 Introduction to Debugging § The control of the cabinet type dehumidification unit has been completed internally, and the indoor panel Check the installation location of external sensitive components (a representative location for humidity in the control can be carried out according to the process requirements.
6. Controller 6.1 General 6.1.1 Controller Terminals: Terminal Description Load Power supply 220VAC 220VAC output Max 1A High fan speed Relay 1--H Medium fan speed 220VAC output Max 1A Relay 2--M Fan coil valve 220VAC output Max 1A Low fan speed;Humidifier Relay 3--L Compressor 220VAC output Max 1A...
6.1.4 Parameters Setting A.General parameters ON/OFF: Short pressto turn on/off the controller :the small OFF appear in the top when the unit is powered off 6.1.5 Icon: and disappear after 3 minut; e s Short pressto to exit during parameters setting. Fan Speed: - Compressor working - Flashing when the...
6.2 Working Mode: 6.4 Fan Control 6.2.1 Dehumidification Working Mode § The initial value is high speed,can be adjusted manually. § EC motor (0~10V) fan has 5 fan speeds,which can be set separately. § AC motor fan speed can be adjusted manually when H04=0: Mode Code H04=0 §...
6.6 Defrost Control (1)Defrost conditions: 6.8 Working Status Display Indoor temperature≦D3,Defrost interval≧D1 (2)Defrost mode: Range Precision Type compressor cycle off & fan runs at high speed -30.0~99.0°C,-22~210°F 0.1°C,1°F Indoor temperature (3)Defrost stop conditions: 1~100% 0.1% Indoor humidity § Defrost time≧D2; 0.0~99.9 0.1g/kg §...
6.12 RS485-2 Modbus communication protocol Function code description: 6.11 Parameters Code Description function 03 – read function 06 – write single function 16 – write multiple Code Parameters Default Precision Range Read Only or Address Object Byte Data Function Code Read/Write 1%-99% Humidity set(dehumidify)
Page 17
6.13、 Device connect Wi-Fi process 1.Connect smart phone to local router’s WIFI. 2. Open smart phone Bluetooth. 3. Download APP “smart life” Scan QR code to download Smartlife App. 6.Press and hold “on/off” button for 10 7. APP will discover the device seconds, until LCD full display.
7. Maintenance 8. Troubleshooting 8.1 Troubleshooting Introduction 7.1 Introduction The purpose of this chapter is to help the operator of the unit to analyze the cause of the failure and The precision dehumidifier can run for a long time and only needs ver y little maintenance. The maintenance of master the method of troubleshooting.