Troubleshooting Of Remote I/O Stations; The Pw Led Does Not Turn On - Mitsubishi Electric MELSEC Q Series User Manual

Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

6.4

Troubleshooting of Remote I/O Stations

The troubleshooting procedures for the remote I/O stations are shown according to the LED status.
For troubleshooting of a remote device station, refer to the following.
User's manual for the remote device station used
6.4.1
Check the following.
The communication cable connected to the power supply is
incorrectly wired.
A communication cable is connected to the LINK connector
of the dedicated power supply or power supply adapter.
A 24VDC supply voltage is outside the specified range.
*1
*2
If the PW LED does not turn on even after the above actions are taken, the possible cause is a hardware failure.
Please consult your local Mitsubishi service center or representative, explaining a detailed description of the problem.
70
Downloaded from
ManualsNet.com

The PW LED does not turn on

Check item
Check for short-circuit, reverse connection, disconnection, and excessive pressure.
Measure a voltage using check terminals on the terminating resistor.
Check terminal 24G
search engine
1
Correct the wiring.*
Connect the cable to the LINK/POWER connector.
Reduce the supply voltage within the specified range.
Check terminal 24V
Action