6 PROGRAMMING
6.2 For Use in Normal System Configuration
6
6 - 2
Downloaded from
ManualsNet.com
System configuration for program explanation
(1) System configuration
Perform the following intelligent function module switch settings in advance.
• Switch 1
0000
• Switch 2
Empty
• Switch 3
Empty
• Switch 4
Empty
• Switch 5
Empty
(2) Program conditions
The programs are written to read the temperatures measured by the
thermocouple (K type) connected to channel 1.
They include write data error code reading and error code resetting programs.
(a) Contents of initial setting
• Used channel.................................................................... CH1
• CH1 Set Value Setting (SV) ............................................. 200
• CH1 Alert1 Mode Setting.................................................. UprLmt Input
• CH1 Alert Set Value1 ....................................................... 500
• CH1 Upper Setting Limiter ............................................... 400
• CH1 Lower Setting Limiter ............................................... 0
(b) Devices used by user
• Set value write command................................................. X0
• Auto tuning execution command
(when GX Configurator-TC is not used) .......................... X1
2
• E
PROM's PID constant read command
(when GX Configurator-TC is used) ................................ X1
• Error code reset command .............................................. X2
• Operation mode setting command .................................. X3
• Temperature detection value output (BCD 4 digits) ........ Y50 to Y5F
• Write data error code storage register............................. D50(D150)
• Read temperature detection value storage register ........ D51
search engine
(CH1: CLEAR)
H
MELSEC-Q