Terminal Block Unit Utba2 - Toshiba TOSDIC-CIE DS Instruction Manual

Hide thumbs Also See for TOSDIC-CIE DS:
Table of Contents

Advertisement

Terminal Block Unit UTBA2
UTBA2 specifications
Model name
Form of mounting
Number of modules that can be mounted
Compatible modules
Compatible option boards
Compatible short bar
External line terminal block
Matching external line size
Maximum current in I/O bus
Accessories
Ability of insulation to withstand voltage
External dimensions
Weight
Item
3. System Configuration Unit and Module
Specification
UTBA2
Exclusively for perpendicular mounting on DIN rail
(fixed in place by M4 screws)
Up to 2 PI/O modules
SAI02, SAI03, SRT01, SAO02
FIVC21, FIVC22 (only SAI02 and SAI03 modules can
be used)
Unnecessary
2 removable type terminal blocks (M3.5 screws 21
terminals relation between screws and terminals
unclear)
2
1.25 mm
or less
24 Vdc-2.2 A (total PI/O modules current
consumption)
1 I/O bus cable ZCS005A0701
1 blank cover FSCV1
500 Vac for 1 minute (between external signal lines,
between external and internal signal lines)
80 W  240 H  77 D mm (this unit alone, excluding
protrusions)
80 W  240 H  120 D mm (with PI/O module
mounted, excluding protrusions)
750 g or less (this unit by itself)
41