8.4 Resetting the positioner

This function resets all start-up and setting parameters as well as the diagnosis to the factory
default settings (see code list in Annex).
Enable configuration:
Configuration is locked again if no settings are entered within 120 seconds.
1. Turn
until Code 3 appears (reading:
No).
2. Press
, the code number 3 blinks.
3. Turn
until YES appears.
4. Press
to confirm (reading: ).
Reset start-up parameters:
1. Turn
until Code 36 appears (reading:
••–••–).
2. Press
, the code number 36 blinks.
3. Turn
until Std appears.
4. Press
to confirm.
All start-up parameters as well as the diag-
nosis are reset to their default values.
Note
Code 36 - diAG allows just the diagnosis data (EXPERTplus) to be reset. Refer to the Operat-
ing Instructions for EXPERTplus valve diagnostics
EB 8384-3 EN
EB 8389 .
u
Operation
Enable configuration
Default: No
Reset
Default: No
8-5