Setting switches

Switch SW1 on the VESDA RS-232 interface daughter card is a bank of eight dip switches. From left to right
SW1-1 through SW1-8. The function of these switches is as follows:
• SW1-1 sets the baud rate for the serial communication line running between the VESDA RS-232 interface card and the 4100 CPU. Set this
switch to ON.
• SW1-2 through SW1-8 set the card address within the 4100 FACP. These switches must be set to the value assigned to the card by the
Programmer. See Figure 3 for a complete list of the switch settings for all of the possible card addresses.
page 3
4100/4120-Series VESDA Interface Cards Installation Instructions
Figure 2: Jumper settings for the VESDA RS-232 interface card
(Figure
2) these switches are designated as
574-050 Rev. N