Appendix

DIP Switch Description

DIP switch definitions for both types of the ConnectUPS
Web/SNMP Cards are listed in Table 4.
Table 4. DIP Switch Modes
SW1
Off
Off
On
On

Jumper 1 (JP1) Settings

The JP1 jumper is found on both the ConnectUPS-X and
ConnectUPS-BD. The JP1 pins are NOT jumpered by
factory-default. Table 5 shows the jumper definitions.
Table 5. JP1 Definitions
Jumper Setting
1 and 2
3 and 4
NOTE
On the ConnectUPS-BD, jumper positions 5 and 6, 7 and 8 are undefined;
DO NOT jumper these positions.
32
ConnectUPS
Web/SNMP Card (X and BD Models) User's Guide
SW2
Description
Off
Operational Mode (default)
On
BOOTP/DHCP Enable Mode (overrides the serial/Telnet
configuration)
Off
Reserved
On
Reserved
Definition
Allows admin to be entered as the password when the
programmed Superuser password has been forgotten
Disables all changes to the card's configuration
:
Rev A www.powerware.com