Page 1
ConnectUPS WEB/SNMP Card User’s Guide X and BD Models www.powerware.com...
Page 2
Hewlett-Packard Company. IBM is a registered trademark of International Business Machines Corporation. Copyright 2002 Powerware Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Powerware...
Page 3
89/336/EEC, Council Directive relating to electromagnetic compatibility 92/31/EEC, Amending Directive 89/336/EEC relating to EMC The EC Declaration of Conformity is available upon request for products with a CE mark. For copies of the EC Declaration of Conformity, contact: Powerware Corporation Koskelontie 13 FIN-02920 Espoo Finland...
Powerware UPS that has an X-Slot The ConnectUPS Web/SNMP Card is available in two models: the ConnectUPS-X for X-Slot UPSs and the ConnectUPS-BD for UPSs with a BestDock slot. Both models can connect to a twisted-pair Ethernet (10/100BaseT) network using an RJ-45 connector.
Page 8
Web browser provides quick visibility of the UPS status. Multiple ConnectUPS Web/SNMP Cards can be monitored simply using free ConnectUPS MultiView software. ConnectUPS Web/SNMP Card (X and BD Models) User’s Guide page, a color-coded Rev A www.powerware.com...
ConnectUPS-X Power Line NetWatch Client NetWatch Client Microsoft Windows 95/98/Me/NT/2000/XP Figure 1. ConnectUPS Web/SNMP Card System Application Diagram ConnectUPS Web/SNMP Card (X and BD Models) User’s Guide Introduction NMS Station Web Browser Ethernet NetWatch Client UNIX/Linux NetWare Rev A www.powerware.com...
Page 10
Introduction ConnectUPS Web/SNMP Card (X and BD Models) User’s Guide Rev A www.powerware.com...
Additional Ethernet Connectors Figure 2. ConnectUPS-X Panel Details COM Port DIP Switch Reset Button Status LED (yellow) ConnectUPS Web/SNMP Card (X and BD Models) User’s Guide Power LED (green) Status LED (yellow) DIP Switch Reset Button COM Port Ethernet Connector...
If you choose to configure your card locally, see “Local Configuration” on page 9. ConnectUPS Web/SNMP Card (X and BD Models) User’s Guide Installation Card Function Description Normal operation with Ethernet traffic...
Web browser, but can be changed from the Telnet utility. If you choose to configure your card remotely, see “Remote Configuration” on page 17. ConnectUPS Web/SNMP Card (X and BD Models) User’s Guide Rev A www.powerware.com...
COM port on your computer. ConnectUPS Web/SNMP Card Serial Cable Figure 4. Cable Connection from Serial Port ConnectUPS Web/SNMP Card (X and BD Models) User’s Guide To TTY port on terminal or COM port on computer Rev A www.powerware.com...
Page 16
1. Web/SNMP Card Settings 2. Reset Configuration to default 3. Restart Web/SNMP Card 4. UPS Pass-Through 0. Exit Please Enter Your Choice =>_ Figure 5. ConnectUPS Web/SNMP Card Main Menu Screen ConnectUPS Web/SNMP Card (X and BD Models) User’s Guide Rev A www.powerware.com...
2. Type to enter the Set the IP Address, Gateway Address and MIB System Group menu. Enter the appropriate settings for your network (see page 14). ConnectUPS Web/SNMP Card (X and BD Models) User’s Guide Local Configuration Rev A www.powerware.com...
Page 18
Telnet utility to adjust any of the configuration settings. The menus are identical to those seen during serial configuration and are password-protected for Superuser access only. ConnectUPS Web/SNMP Card (X and BD Models) User’s Guide through ). Each Rev A www.powerware.com...
Page 19
1. Web/SNMP Card Settings 2. Reset Configuration to default 3. Restart Web/SNMP Card 4. UPS Pass-Through 0. Exit Please Enter Your Choice =>0 Figure 7. Exiting the Configuration Program ConnectUPS Web/SNMP Card (X and BD Models) User’s Guide Local Configuration Rev A www.powerware.com...
ConnectUPS Web/SNMP Card, use this function to enable HTTP Security Control. NOTE To obtain an IP address using BOOTP/DHCP (instead of serial configuration), set DIP Switch 2 on the front panel to the ON position (OFF is the default). ConnectUPS Web/SNMP Card (X and BD Models) User’s Guide...
Web/SNMP Card performs during AC Fail and Low Battery events (option ). This information is accessible via the HTTP interface for easy modification after the card is on the network. ConnectUPS Web/SNMP Card (X and BD Models) User’s Guide Rev A www.powerware.com...
Card. This information is accessible via the HTTP interface for easy modification after the card is on the network. Back to Main Menu Type to return to the Main Menu screen (see Figure 7 on page 13). ConnectUPS Web/SNMP Card (X and BD Models) User’s Guide Rev A www.powerware.com...
192.72.173.20 is an example IP address for the computer. NOTE Refer to your operating system documentation for additional details on how to add a routing condition. ConnectUPS Web/SNMP Card (X and BD Models) User’s Guide Rev A www.powerware.com...
Web/SNMP Card IP address (the default is 192.168.7.18). 2. The home page of the ConnectUPS Web/SNMP Card appears (see Figure 8). Figure 8. ConnectUPS Web/SNMP Card Home Page ConnectUPS Web/SNMP Card (X and BD Models) User’s Guide Rev A www.powerware.com...
Password (the default user name and password is admin). Figure 9. ConnectUPS Web/SNMP Card Configuration Page ConnectUPS Web/SNMP Card (X and BD Models) User’s Guide from the menu at the top of the to set Web/SNMP Card Configuration and log in with the Username...
Page 26
Refer to the remainder of this user’s guide and the online help for detailed information about each menu selection. ConnectUPS Web/SNMP Card (X and BD Models) User’s Guide ConnectUPS Web/SNMP Card IP for the network. Gateway Address of the network.
UPS has been bypassed) red indicates a low battery condition and shutdown is imminent black indicates a loss of communication between the UPS and the ConnectUPS Web/SNMP Card ConnectUPS Web/SNMP Card (X and BD Models) User’s Guide Rev A www.powerware.com...
NOTE Once you have become a Superuser, it is important to completely exit the browser if you wish to set the security level back to the standard read-only level. ConnectUPS Web/SNMP Card (X and BD Models) User’s Guide Rev A www.powerware.com...
4. Click Set Values 5. Once the values are set, select at the top of the home page. ConnectUPS Web/SNMP Card (X and BD Models) User’s Guide Load Load Segment to Restart and set Delay Before to a valid delay value to allow the UPS...
You can change the Identification Information field to a more recognizable sender user name by accessing the Identification ConnectUPS Web/SNMP Card (X and BD Models) User’s Guide UPS Power Management , followed by from the menu at the top of the...
Page 32
Web/SNMP Card Event Log. Review the Event Log within a few minutes of testing the e-mail to see if any errors are logged. ConnectUPS Web/SNMP Card (X and BD Models) User’s Guide on the Web/SNMP Card The default The ConnectUPS Web/SNMP...
NOTE For security, it is recommended to change the Write Access Managers table using specific IP addresses and nonstandard community strings. ConnectUPS Web/SNMP Card (X and BD Models) User’s Guide UPS Power Management Initiate Battery Test to start the process.
The ConnectUPS Web/SNMP Card supports several event-related traps, that can be reported to the SNMP network management software. Refer to the MIB files found on the supplied CD-ROM for more information. ConnectUPS Web/SNMP Card (X and BD Models) User’s Guide Rev A www.powerware.com...
UPS power is turned off. When the power returns, the UPS automatically restarts after a 30-second delay and supplies power to the load. ConnectUPS Web/SNMP Card (X and BD Models) User’s Guide UPS Power Management Rev A www.powerware.com...
Page 36
UPS Power Management ConnectUPS Web/SNMP Card (X and BD Models) User’s Guide Rev A www.powerware.com...
(maximum) Size (L x W x H) ConnectUPS-X: 12 cm x 11.4 cm x 39 cm (4.72 x 4.52 x 1.52) ConnectUPS-BD: 13.4 cm x 81 cm x 33 cm (5.32 x 3.22 x 1.32) Weight 200 gm (7 oz)
Superuser password has been forgotten 3 and 4 Disables all changes to the card’s configuration NOTE On the ConnectUPS-BD, jumper positions 5 and 6, 7 and 8 are undefined; DO NOT jumper these positions. ConnectUPS Web/SNMP Card (X and BD Models) User’s Guide...
5. Activate the checkbox by the ConnectUPS Web/SNMP Card(s) to be upgraded (up to four cards at a time under most network conditions). ConnectUPS Web/SNMP Card (X and BD Models) User’s Guide Appendix , and then entering the path and which instructs the utility to Discover Rev A www.powerware.com...
: Date of failure or problem : Symptoms of failure or problem : Customer return address and contact information ConnectUPS Web/SNMP Card (X and BD Models) User’s Guide Modify and select the binary Filename to start the process. After the process...
Date of Purchase. If, in Powerware Corporation’s opinion, the electronics fails to meet its published specifications due to a defect in material and workmanship covered by this warranty, Powerware Corporation will repair or replace the warranted Unit at no cost to the customer for parts and labor.
Powerware Corporation prompt notice thereof and if requested by Powerware Corporation, the user shall return the warranted Unit or parts thereof to the plant or service station designated by Powerware Corporation for inspection by Powerware Corporation.