VERITAS NetBackup 5330 Hardware Service Procedure page 6

Sas data cable replacement
Hide thumbs Also See for NetBackup 5330:

Advertisement

Removing and replacing NetBackup 5330 storage shelf SAS data cables
Warning: Remove only one SAS data cable at a time.
To remove and replace a NetBackup 5330 storage shelf SAS data cable
Do one of the following:
To replace a SAS data cable between the Primary Storage Shelf and an Expansion Storage
Shelf, see
Storage
To replace a SAS data cable between the Expansion Storage Shelfs, see
data cable between the Expansion Storage
Replacing a SAS data cable between the Primary Storage Shelf and an Expansion
Storage Shelf
To replace a SAS data cable between the Primary Storage Shelf and an Expansion Storage
Shelf
1
At the rear of the Primary Storage Shelf, determine the SAS data cable that you want to replace.
Note the SAS port of the cable you want to replace.
2
Gently pull the SAS data cable connector from the SAS port on the Primary Storage Shelf.
3
At the rear of the Expansion Storage Shelf, note the SAS port of the cable you want to replace.
4
Gently pull the SAS data cable connector from the SAS port on the second Expansion Storage
Shelf.
5
Obtain the replacement SAS data cable.
6
Gently plug one end of the SAS data cable into the SAS port on the Primary Storage Shelf where
you removed the previous cable.
7
Gently plug the other end of the SAS data cable into the SAS port on the Expansion Storage
Shelf where you removed the previous cable.
End of procedure
Replacing a SAS data cable between the Expansion Storage Shelfs
To replace a SAS data cable between the Expansion Storage Shelfs
1
At the rear of the first Expansion Storage Shelf, determine the SAS data cable that you want to
replace. Note the SAS port of the cable you want to replace.
2
Gently pull the SAS data cable connector from the SAS port on the first Expansion Storage Shelf.
3
On the rear of the second Expansion Storage Shelf, note the SAS port of the cable you want to
replace.
4
Gently pull the SAS data cable connector from the SAS port on the second Expansion Storage
Shelf.
HSP 151 Storage shelf SAS cable replacement