Slow Speed Code; Polarization Motor Option - Dawn CONTROL-1500A Manual

Remote controlled antenna controller for single axis antennas
Table of Contents

Advertisement

CONTROL-1500A Single Axis Antenna Controller
POS
REMOTE ENABLE:1
0-NO, 1-yes
The Comm Address item selects the address of the communications port. Valid values for this
parameter are 49 to 111.
POS
COMM ADDRESS: 50
49 – 111
The Baud (100s) item selects the baud rate that the controller's serial port will be initialized to.
Valid values for this parameter are 12 (1200 baud), 24 (2400 baud), 48 (4800 baud) and 96
(9600 baud).
POS
BAUD (100s):96
12,24,48,96
4.9.3

Slow Speed Code

The Slow Speed CONFIG item can be used to set the slow speed code. Please refer to
section 3.5 for more information on the slow speed system. The range of values for this
parameter is 1 to 254. Higher numbers give a faster rate of slow speed movement. (A slow
speed code of 254 will disable the slow speed system - all movement will occur at fast speed.)
For most motor/sensor combinations, a slow speed code in the range of 140 to 175 is
appropriate. If the slow speed code is changed, test the slow speed system to insure that the
selected value yields reasonable results. Access to this CONFIG mode item is allowed only
when the Expert Access flag is set.
POS
SLOW SPEED:254
0 – 254
4.9.4

Polarization Motor Option

The RC2KPOL option allows the CONTROL-1500 to control a 12 or 24 volt polarization motor with
potentiometer based position feedback. If this option is present, a 5 terminal orange connector
will be found on the upper left-hand corner of the back panel. The CONFIG mode items
described in this section are used to configure the controller to work with the RC2KPOL option.
Access to these CONFIG mode items is allowed only if the Expert Access flag is set. The
24vdc Rot Feed item is the controlling item for access to the other items described in this
section.
The 24vdc Rot Feed CONFIG mode item is used to inform the controller of whether or not a
polarotor servo motor is present in the system. If the RC2KPOL option is installed this
parameter should be set to YES (see section 3.3).
DAWNco • 3340 S. Lapeer Rd • Orion, MI 48359-1320 • Ph (248) 391-9200 • Fax (248) 391-9207 • sales@DAWNco.com
POL
SS
CFG
MODE
POL
SS
CFG
MODE
POL
SS
CFG
MODE
POL
SS
CFG
MODE
Chapter 4
Modes Function Description
47