Product Specifications - Delta DAC-633 Installation Manual

Table of Contents

Advertisement

Delta Controls

Product Specifications

Power Requirements
Power Consumption
Ambient Ratings
Communication Ports
Inputs
Outputs
Technology
Listings
Compliance
Page 10 of 12
24 VAC, Class 2, 60Hz
12 VA
48 VA max (with fully loaded Binary Outputs (Triacs))
32° to 131°F (0° to 55°C), 10 to 90% RH (non condensing)
NET1
BACnet MS/TP (RS-485)
Communication: 9600, 19200, 38400, 76800 bps (Default)
Maximum of 99 controllers
NET2
LINKnet
Communication: 76800 bps
Maximum of 6 LINKnet controllers including up to two DFM
controllers
Service
RJ-11 Jack
Port
Used with Delta Controls service tool devices (for example,
CON-768)
6 Universal Inputs (10 bit), jumper configurable for the following input
types:
0-5 VDC
0-10 VDC
10 KΩ Thermistor
Dry Contact (using 10 KΩ Thermistor jumper setting
4-20 mA
3 Analog Outputs c/w LED status indication
0-10 VDC @ 20mA maximum per output
Software configurable as binary or analog
3 Binary Triac Outputs c/w LED status indication
Switching 24VAC@0.5 Amp maximum per output
Leakage Current per Triac is 160 µA
32 bit processor
1 MB (8 megabit) Flash Memory
256 KB SRAM memory
UL 916 Listed
BTL Listed
UL 864 Listed (DAC-633-UL864 model only)
CE
FCC

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dsc-633

Table of Contents