Baur PD-TaD 62 User Manual page 40

Portable diagnostics system
Table of Contents

Advertisement

Connecting the system
No.
Cable
On the laptop:
4
USB cable
5
Ethernet cable
At the PD-TaD 62:
6
PoE cable
7
8
HV connection cable of
the VLF HV generator
9
Short-circuit cable of
PD-TaD 62
At the far end of the test object:
10
11
At the near end of the test object:
12
13
14
HV connection cable of
PD-TaD 62
At the near and far end of the test object:
15
40 / 114
Step
For the remote control of the VLF HV generator: Use a USB cable to
connect the laptop to the VLF HV generator.
Use the supplied Ethernet cable to connect the laptop to the Power Box
(Laptop port).
If you do not want to run the laptop off its battery, connect the laptop to the
Power Box to establish a power supply. To do so, use the connection cable
with the C14G plug.
Connect the PoE cable:
to the Power Box (PD Detector port) and
to PD-TaD 62 (Power Box port)
This is used for power supply and data transmission at the same time.
Connect the HF filter to the HV IN port.
Further information: Chapter Connecting the HF filter to the PD-TaD 62 (on
page 55)
Connect the HV connection cable to the HF filter at the HV IN port.
Further information: Chapter Connecting the HF filter to the PD-TaD 62 (on
page 55)
On the PD-TaD 62, remove the short-circuit cable from ports HV IN and
HV OUT.
Clean the cable termination of the phase to be tested carefully.
Attach the anti-corona hoods of the anti-corona protection device to the
cable termination of the phase to be tested.
Clean the cable termination of the phase to be tested carefully.
Attach the anti-corona hoods of the anti-corona protection device to the
cable termination of the phase to be tested.
Connect the PD-TaD 62 (HV OUT port) to the phase to be tested.
To do this, select the shorter of the two supplied HV connection cables.
Place the HV connection cable as far away as possible from the adjacent
live and earthed parts.
Remove the earthing and short-circuit connection from the phase to be
tested.
Make sure that the phases not being tested are earthed and short-circuited.
PD-TaD 62
822-187-3