Baur PD-TaD 62 User Manual page 36

Portable diagnostics system
Table of Contents

Advertisement

Connecting the system
Required equipment
PD-TaD incl. connection cables
HF filter
PoE cable
Laptop incl. Ethernet and USB cable
Anti-corona protection
Note:All the necessary connection cables and connecting elements are included in the
standard delivery.
Procedure
Important:
 To keep the connection cable between the PD-TaD and the test object short, place the
PD-TaD as close as possible to the test object.
To avoid interference due to partial discharge at the connection point, make sure the PD-
TaD is placed a sufficient distance away from metal and live parts.
If the connection point is higher up, put the PD-TaD on a substructure. Further
information: Chapter Securing the PD-TaD 62 to the cross beam (on page 33)
 Keep all connections as short as possible.
 Lay out the connection cables in such a way that no loops are created.
The numbering in the table gives the sequence of steps for connecting the test object.
No.
Cable
1
Protective earthing
cable of the VLF HV
generator
2
Protective earthing
cable of PD-TaD 62
(flat copper strip)
36 / 114
Step
Earth the VLF HV generator.
Further information: User manual for the respective VLF HV generator
Connect the PD-TaD 62 to the station earth (close to the test object cable
screen).
Further information: Chapter Earth system (on page 35)
PD-TaD 62
822-187-3