Pd-Tad - Baur PD-TaD 62 User Manual

Portable diagnostics system
Table of Contents

Advertisement

PD-TaD 62

3.3
PD-TaD
No.
Designation
on device
1
2
3
4
5
6
7
HV OUT
8
HV IN
9
VLF Generator
PWR
10
PD
822-187-3
Element
PD measuring unit
Protective earthing
connection
HV coupling unit with
integrated measurement
impedance
Short-circuit cable
Port for the short-circuit
cable
Handles
HV output
HV input
Port
LED
LED
Function
Is used for the measurement and location of partial
discharges
Is used to connect the protective earthing
The earthing connection for the short circuit cable is
located on the side of the protective earthing connection.
Is used to couple out high-frequency PD pulses via a
measurement impedance (in accordance with IEC 60270)
and convert them into equivalent voltage signals
Is used to short-circuit the HV ports HV IN and HV OUT
and the protective earthing (for the transportation and
storage of the PD-TaD)
Is used to connect the short circuit cable to the HV ports
HV IN and HV OUT
Two connection sockets are provided on each of the HV
connectors for the short-circuit cable: on the top and on
the side.
Are used to lift and carry the PD-TaD
Is used to connect the PD-TaD to the test object
Is used to connect the PD-TaD to the VLF HV generator
Is used to connect the PD-TaD to the VLF HV generator
Does not come on: PD-TaD is not supplied with
voltage.
Is on continuously: PD-TaD is supplied with voltage.
Does not come on: No measurement performed
Flashing:
PD events are being received.
The LED lights up for half a
second if a PD event occurs.
Product information
17 / 114