Configuring/address space
4.4 Parameters
Parameter
Set output DQ
Substitute value for DQ
1
Count direction
1
Pulse duration [ms/10]
1
Behavior of DI
Edge selection
1
Filter time
1
Frequency
1
Comparison value 0
1
Comparison value 1
1
36
Value range
Use by user program
•
Between comparison value and high
•
counting limit
Between comparison value and low
•
counter limit
Between comparison value 0 and 1
•
Not between comparison value 0 and
•
1
At comparison value for a pulse
•
duration
After set command from CPU until
•
comparison value
0
•
1
•
Forward
•
Backward
•
In both directions
•
0...65535
Capture
•
Digital input without function
•
At rising edge
•
At falling edge
•
At rising and falling edge
•
Deactivated
•
0.05 ms
•
0.1 ms
•
0.4 ms
•
0.8 ms
•
1.6 ms
•
3.2 ms
•
12.8 ms
•
20 ms
•
Once
•
Periodic
•
-2147483648...2147483647
-2147483648...2147483647
Default setting
DQ0, DQ1: Between
comparison value and
high counting limit
DQ0, DQ1: 0
In both directions
5000 (corresponds to
0.5 s)
DI0, DI1: Digital input
without function
At rising edge
0.1 ms
Once
0
10
Technology module TM PosInput 1 (6ES7138-6BA00-0BA0)
Manual, 02/2014, A5E33015755-AA
Re-
configuration
in RUN
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes