3:3 phase configuration
Please use the below diagram: (3.a)
• For 3:3 configuration, the cables for Garun 10KL (PN
UP33TOP110KGAAZ02B) should be able to withstand over 16A current
for Input and Output phase, 28A for Neutral, 32A for batteries and 16A for
Ground. Please use corresponding thickness for each wire.
• For 3:3 configuration, the cables for Garun 20KL (PN
UP33TOP120KGAAZ02B) should be able to withstand over 32A current
for Input and Output phase, 55A for Neutral, 62A for batteries and 32A for
Ground. Please use corresponding thickness for each wire.
3:1 phase configuration
Please use the below diagram: (3.b)
14
NOTE!
For 3:1 configuration, you need to connect only one phase to Bypass Input
connector and Output connector. Each of the three connectors from Bypass input
and from Output needs to be connected with cables.
• For 3:1 configuration, the cables for Garun 10KL (PN
UP33TOP110KGAAZ02B) should be able to withstand over 16A current for
Input phase, over 46A for Output phase, 28A for Neutral, 32A for batteries
and 16A for Ground. Please use corresponding thickness for each wire.
• For 3:1 configuration, the cables for Garun 20KL (PN
UP33TOP120KGAAZ02B) should be able to withstand over 32A current for
Input phase, over 92A for Output phase, 55A for Neutral, 62A for batteries
and 32A for Ground. Please use corresponding thickness for each wire.
1:1 phase configuration
Please use the below diagram: (3.c)
NOTE!
For 1:1 configuration, you need to connect only one phase to Input, Bypass
Input connector and Output connector. Each of the three connectors from Input,
Bypass Input and from Output needs to be connected with cables.
• For 1:1 configuration, the cables for Garun 10KL (PN
UP33TOP110KGAAZ02B) should be able to withstand over 48A current for
Input phase, over 46A for Output phase, 85A for Neutral, 32A for batteries
and 48A for Ground. Please use corresponding thickness for each wire.
• For 1:1 configuration, the cables for Garun 20KL (PN
UP33TOP120KGAAZ02B) should be able to withstand over 96A current for
Input phase, over 92A for Output phase, 165A for Neutral, 62A for batteries
and 96A for Ground. Please use corresponding thickness for each wire.