ON/OFF Charger
It will show "Turn on Charger?" when charger is off.
It will show "Turn off Charger?" when charger is on.
Touch "YES" to turn on or off the charger. Then, the screen will return to
main screen.
Touch "Back" to return to CONTROL screen immediately or "No" to cancel
this operation and back to CONTROL screen.
Turn on Charger
3.2.3. Measure screen
Touch the icon
to enter measure page. Touch the icon
browse information. Touch the icon
icon
to go back to previous menu.
Measure screen page 1
22
Turn off Charger
or
to
to return to main screen. Touch the
LINE VOL: The real time value of R, S and T phase voltage, RS, ST, TR voltage
and input frequency.
INVERTER VOL: The real time value of R, S and T inverter voltage, RS, ST and
TR voltage and frequency.
BYPASS VOL: The real time value of R, S and T bypass voltage, RS, ST and TR
voltage and frequency.
OUTPUT VOL: The real time value of R, S and T output voltage, RS, ST and
TR voltage and frequency
Measure screen page 2
OUTPUT W: R, S and T output power in watt.
OUTPUT VA: R, S and T output power in VA.
OUTPUT W (%): R, S and T output power watt in percentage.
OUTPUT VA (%): R, S and T output power VA in percentage.
Total watt and VA: Total output load in watt and VA.
BATT Voltage/Bus Voltage/Charging Current/Discharging Current: The real
time value of DC related information.
Temperature: Temperature of R, S and T phases.