2.3 DCS 600 Overload Capability
To match a drive system's components as efficiently as possible to the driven
machine's load profile, the armature power converters DCS 600 can be dimensio-
ned by means of the load cycle. Load cycles for driven machines have been defi-
ned in the IEC 146 or IEEE specifications, for example.
The currents for the DC I to DC IV types of load (see diagram on the following page) for the power converter
modules are listed in the table below.
Unit type
I
DC I
contin-
uous
400 V / 500 V
[A]
DCS 60x-0025-41/51
25
DCS 60x-0050-41/51
50
DCS 60x-0075-41/51
75
DCS 60x-0100-41/51
100
DCS 601-0140-41/51
125
DCS 602-0140-41/51
140
DCS 601-0200-41/51
180
DCS 602-0200-41/51
200
DCS 601-0250-41/51
225
DCS 602-0250-41/51
250
DCS 601-0350-41/51
315
DCS 602-0350-41/51
350
DCS 601-0450-41/51
405
DCS 602-0450-41/51
450
DCS 601-0520-41/51
470
DCS 602-0520-41/51
520
DCS 601-0680-41/51
610
DCS 602-0680-41/51
680
DCS 601-0820-41/51
740
DCS 602-0820-41/51
820
DCS 601-1000-41/51
900
DCS 602-1000-41/51
1000
DCS 60x-1203-41/51
1200
DCS 60x-1503-41/51
1500
DCS 60x-2003-41/51
2000
DCS 60x-2053-51
2050
DCS 601-2503-41/51
2500
DCS 602-2503-41/51
2500
DCS 601-3003-41/51
3000
DCS 602-3003-41/51
3000
DCS 60x-3303-41/51
3300
DCS 60x-4003-41/51
4000
DCS 60x-5203-41/51
5200
600 V / 690 V
DCS 60x-0050-61
50
DCS 601-0110-61
100
DCS 602-0110-61
110
DCS 601-0270-61
245
DCS 602-0270-61
270
DCS 601-0450-61
405
DCS 602-0450-61
450
DCS 60x-0903-61/71
900
DCS 60x-1503-61/71
1500
DCS 601-2003-61/71
2000
DCS 60x-2053-61/71
2050
DCS 601-2503-61/71
2500
DCS 602-2503-61/71
2500
DCS 601-3003-61/71
3000
DCS 602-3003-61/71
3000
DCS 60x-3303-61/71
3300
DCS 60x-4003-61/71
4000
DCV 60x-4803-61/71
4800
790 V
DCS 60x-1903-81
1900
DCS 601-2503-81
2500
DCS 602-2503-81
2500
DCS 601-3003-81
3000
DCS 602-3003-81
3000
DCS 60x-3303-81
3300
DCS 60x-4003-81
4000
DCS 60x-4803-81
4800
1000 V
DCS 60x-2053-91
2050
DCS 60x-2603-91
2600
DCS 60x-3303-91
3300
DCS 60x-4003-91
4000
1190 V
x=1 → 2-Q; x=2 → 4-Q
I
I
DC II
100 %
150 %
100 %
15 min
60 s
15 min
[A]
[A]
24
36
23
44
66
42
60
90
56
71
107
69
94
141
91
106
159
101
133
200
132
149
224
146
158
237
155
177
266
173
240
360
233
267
401
258
317
476
306
352
528
340
359
539
347
398
597
385
490
735
482
544
816
538
596
894
578
664
996
648
700
1050
670
766
1149
736
888
1332
872
1200
1800
1156
1479
2219
1421
1550
2325
1480
1980
2970
1880
2000
3000
1930
2350
3525
2220
2330
3495
2250
2416
3624
2300
2977
4466
2855
3800
5700
3669
44
66
43
79
119
76
87
130
83
193
290
187
213
320
207
316
474
306
352
528
340
684
1026
670
1200
1800
1104
1479
2219
1421
1520
2280
1450
1940
2910
1840
1940
2910
1870
2530
3795
2410
2270
3405
2190
2416
3624
2300
3036
4554
2900
3734
5601
3608
1500
2250
1430
1920
2880
1820
1910
2865
1850
2500
3750
2400
2250
3375
2160
2655
3983
2540
3036
4554
2889
3734
5601
3608
1577
2366
1500
2000
3000
1900
2551
3827
2428
2975
4463
2878
Data on request
3ADW000072R0501_DCS600_System_description_e_e
I
DC III
DC IV
150 %
100 %
200 %
120 s
15 min
10 s
[A]
35
24
48
63
40
80
84
56
112
104
68
136
137
90
180
152
101
202
198
110
220
219
124
248
233
130
260
260
147
294
350
210
420
387
233
466
459
283
566
510
315
630
521
321
642
578
356
712
732
454
908
807
492
984
867
538
1076
972
598
1196
1005
620
1240
1104
675
1350
1308
764
1528
1734
1104
2208
2132
1361
2722
2220
1450
2900
2820
1920
3840
2895
1790
3580
3330
2280
4560
3375
2080
4160
3450
2277
4554
4283
2795
5590
5504
3733
7466
65
40
80
114
75
150
125
82
165
281
169
338
311
187
374
459
282
564
510
313
626
1005
594
1188
1656
1104
2208
2132
1361
2722
2175
1430
2860
2760
1880
3760
2805
1740
3480
3615
2430
4860
3285
2030
4060
3450
2277
4554
4350
2950
5900
5412
3700
7400
2145
1400
2800
2730
1860
3720
2775
1710
3420
3600
2400
4800
3240
2000
4000
3810
2485
4970
4334
2933
5866
5412
3673
7346
2250
1471
2942
2850
1922
3844
3642
2458
4916
4317
2918
5836
Table 2.3/1:
Power converter module
currents with corresponding
load cycles.
The characteristics are
based on an ambient tem-
perature of max. 40°C and
an elevation of max. 1000 m
a.s.l.
II F 2-7