Effective: May 2005
Note: On a 510 trip unit, the 7-position external harness interlocking short-
ing plus is considered the external harness. (See Figure 10).
Figure 10. External Harness Plug.
Figure 11. RSM Connected to the Trip Unit and External Harness.
D. Use the wire ties supplied to secure the RSM to the wiring
harnesses and / or trip unit to keep it away from any moving
parts within the breaker or cell.
For more information visit: www.EatonElectrical.com
Arcflash Reduction Maintenance Switch
5. Completion of the Arcflash Reduction
Maintenance Switch Installation
Step 1: Installing the Arcflash Reduction Maintenance
Switch Mode Selector Switch, Indicator Light, and
Battery Holder
Figure 12. Overview: Typical Installation of the Arcflash Reduction
Maintenance Switch Mode Selector Switch, Indicator Light, and
Battery Holder.
Each installation of the Arcflash Reduction Maintenance Switch
mode selector switch, indicator light, and battery holder may vary
due to the type of breaker, type of cell, or components / options
mounted in or on the cell, etc. Because of these factors, the pro-
cedures in this section are general in nature. However, there are
some basic guidelines that should be considered and followed dur-
ing installation of the Arcflash Reduction Maintenance Switch
mode selector switch, indicator light, and battery holder.
In most cases, mounting the mode selector switch, indicator light,
and battery holder to the cell door, opposite to the cell door
hinges, is the best alternative.
In certain DS applications, it may not be possible to mount the
mode selector switch, battery holder, and indicator light on the
cell door due to interference problems when the breaker is racked
out in the "test" position and the cell door closed. In this case, it is
necessary to mount the components to the "accessory panel" or
drawer above the enclosure. See Figure 13.
Figure 13. Alternate Mounting Location on Certain DS
Applications.