Arcflash Reduction Maintenance Switch
Application and Installation
Figure 20. Mode Selection Switch and LOTO Installed on the
Mounting Surface.
I. When viewed from the rear of the indicator light assembly,
move the yellow locking tab to the right, then remove the
indicator light body from the indicator light contact block.
Remove the lock nut from the indicator light body.
J. Insert the indicator light through the hole in the mounting sur-
face. Secure the indicator light to the mounting surface using
the lock nut just removed. Next, align the indicator light con-
tact block assembly with the indicator light housing. The con-
tact block assembly is "self locking". Insert the contact block
assembly into the indicator light until the locking "click" is
heard. Ensure it is locked into place.
Figure 21. Indicator Light Contact Block Assembly "Locked" on
the Indicator Light Housing.
IL01906001E
For more information visit: www.EatonElectrical.com
Effective: May 2005
Figure 22. Indicator Light Installed on the Mounting Surface.
K. Insert the battery holder through the hole in the mounting sur-
face cut in Step C. Make sure the locking tab for the battery
compartment is facing downward. Align the holes in the bat-
tery holder with the pilot holes drilled earlier in the mounting
surface, then secure the battery holder to the mounting sur-
face using the (4) .138-32 × .375" hex head/slotted thread
cutting screws supplied.
Figure 23. Battery Holder Secured to the Mounting Surface.
L. Install the "Warning" and "Circuit Active" labels on the
mounting surface near the mode selector switch.