Ratings And Specifications; Check Switch Ratings Before Installation; Ratings - Eaton Edison Cooper Power Series Installation And Operation Instructions Manual

Single-phase vacuum capacitor switch
Table of Contents

Advertisement

Edison™ Single-Phase Vacuum Capacitor Switch

Ratings and specifications

Check switch ratings before installation

The Edison capacitor switch must be applied within its
specified ratings. Check data plate ratings and compare with
the system characteristics at the point of application prior to
installation. Table 1 list the ratings and specifications for the
Edison capacitor switch.
Table 1 . Ratings and specifications
Voltage class
Switch type
Rated maximum voltage, 50/60 Hz
Ungrounded capacitor banks, L-L (kV)
Solidly grounded capacitor banks, L-L (kV)
Impulse withstand voltage
Open contact kV (BIL)
Line to ground (kV BIL)
Withstand voltage, 60 Hz
Power Frequency Dry Withstand (kV)
Power Frequency Wet Withstand (kV)
Continuous current 50/60 Hz (A)
Capacitive switching current 50/60 Hz (A)
Fault making peak current (A)
Symmetrical fault making current (A)
Withstand peak current (A)
Short-time symmetrical withstand current (A)
High frequency transient making peak current (A)
Rated transient inrush frequency (Hz)
Creepage distance
Terminal to terminal (mm)
Terminal to ground (mm)
Operating voltage range, 50/60 Hz
110/120 Vac (V)
240 Vac (V)
Nominal control current
110/120 Vac for 100 msec (A)
240 Vac for 100 msec (A)
Weight (lb/kg)
Operating temperature range
Mechanical operations
* The 15.6 kV rated Edison Capacitor Switch is available with an optional High Frequency Transient Making Peak Current of 12 kA. Contact factory for additional information.
** Contact factory for more information regarding dc control voltages.
N
otee:
The durability of the Edison capacitor switch was demonstrated by completing a minimum of 50,000 mechanical
operations after performing the Mechanical Life Test in accordance with IEEE Std C37 .66™-2005 standard. One
operation is defined as one close and one open operation.
2
InstallatIon and operatIon InstructIons MN230007EN February 2017
15 kV
ECS15-95
15.6
15.6
95
95
60
50
200
200
15,000
6,000
15,000
4,500
9,000
6,000
440
498
**
75 – 130
150 – 260
9
6
32/14
-40 °C to +60 °C
50,000

Ratings

All ratings meet or exceed values in IEEE Std C37 .66™-2005
standard for a distribution-class switch, where applicable.
25 kV
ECS15-125
ECS25-125
15.6
25
27
25
95
125
125
125
60
60
50
50
200/400
200
200/400
200
15,000
15,000
6,000
6,000
15,000
15,000
4,500
4,500
9,000/12,000
9,000
*
6,000
6,000
600
813
610
610
75 – 130
75 – 130
150 – 260
150 – 260
9
9
6
6
33/15
33/15
-40 °C to +60 °C
-40 °C to +60 °C
50,000
50,000
ECS25-150
15.6
38
125
150
70
60
200
200
15,000
6,000
15,000
4,500
9,000
6,000
813
813
75 – 130
150 – 260
9
6
34/16
-40 °C to +60 °C
50,000