INSTALLATION PROCEDURES
2.
Electrical Service Specifications
Model DE30 lb, Electrical, Gas and Steam (24 KW For Electric Heater)
IMPORTANT: 208 V AC and 220-240 V AC ARE NOT THE SAME. When ordering, specify exact voltage.
NOTES: A. Fuse ratings are dual element-time-delay-current limiting, class RK1 or RK5 only.
B. Circuit breakers are thermal magnetic (industrial) type only. For others, calculate/ verify correct breaker
size according to appliance amp draw rating and type of breaker used.
C. Circuit breakers for 3 Phase dryers must be 3-pole type.
Service
Phase
Voltage
Gas, Steam
200-240
1
200-240
3
380-415
3
440-480
3
Model DE50 lb, Electrical, Gas and Steam (24 KW For Electric Heater)
IMPORTANT: 208 V AC and 220-240 V AC ARE NOT THE SAME. When ordering, specify exact voltage.
NOTES: A. Fuse ratings are dual element-time-delay-current limiting, class RK1 or RK5 only.
B. Circuit breakers are thermal magnetic (industrial) type only. For others, calculate/ verify correct breaker
size according to appliance amp draw rating and type of breaker used.
C. Circuit breakers for 3 Phase dryers must be 3-pole type.
Service
Phase
Voltage
Gas, Steam
200-240
1
200-240
3
380-415
3
440-480
3
Model DE75 lb, Electrical, Gas and Steam (36 KW For Electric Heater)
IMPORTANT: 208 V AC and 220-240 V AC ARE NOT THE SAME. When ordering, specify exact voltage.
NOTES: A. Fuse ratings are dual element-time-delay-current limiting, class RK1 or RK5 only.
B. Circuit breakers are thermal magnetic (industrial) type only. For others, calculate/ verify correct breaker
size according to appliance amp draw rating and type of breaker used.
C. Circuit breakers for 3 Phase dryers must be 3-pole type.
Service
Phase
Voltage
Gas, Steam
200-240
1
200-240
3
380-415
3
440-480
3
*AWG Stranded Type Wire...for individual lengths less than 100 feet.
(Motor lead type wire is recommended.)
Table 3-1 Electric Service Specifications
Approx.
Amp Draw
Elec.
5.8
106
16AWG/1.5sq.mm.
4.6
71.2
16AWG/1.5sq.mm.
3.1
38.6
16AWG/1.5sq.mm.
2.8
33.3
16AWG/1.5sq.mm.
Approx.
Amp Draw
Elec.
5.8
-
16 AWG/1.5sq.mm.
8.0
74.6
14 AWG/2.5sq.mm.
5.0
41.5
16 AWG/1.5sq.mm.
4.4
35.9
16 AWG/1.5sq.mm.
Approx.
Amp Draw
Elec.
10.6
-
14 AWG/2.5sq.mm.
8.0
108.0
14 AWG/2.5sq.mm.
5.0
59.7
16 AWG/1.5sq.mm.
4.4
51.6
16 AWG/1.5sq.mm.
Wire Size
Gas, Steam
2AWG/35sq.mm.
4AWG/25sq.mm.
8AWG/10sq.mm.
8AWG/10sq.mm.
Wire Size
Gas, Steam
4AWG/25sq.mm.
8AWG/10sq.mm.
8AWG/10sq.mm.
Wire Size
Gas, Steam
2AWG/35sq.mm.
6AWG/16sq.mm.
6AWG/16sq.mm.
3-11
Circuit
Breaker
Elec.
Gas, Steam
10
10
10
10
Circuit
Breaker
Elec.
Gas, Steam
-
15
15
15
10
Circuit
Breaker
Elec.
Gas, Steam
-
15
15
10
10
Elec.
125
100
50
50
Elec.
-
100
50
50
Elec.
-
125
75
75