5 Connection test

5.1 Switching on VIBGUARD IIoT

Switch on the power supply for the CMS.
l
The system module starts up and launches the measuring configuration that is currently loaded on the sys-
l
tem.
Check the LED status on the system module.
l
The system is operational if the system LED lights up green. Observe the LEDs on the analog channels for fault mes-
sages
("LED displays on the system module" on page

5.2 Establishing a connection

The connection between VIBGUARD IIoT and the notebook is established via the network connection.
The network cable on the VIBGUARD IIoT is not suitable for a direct connection between the notebook and
VIBGUARD IIoT as it is wired one to one. A direct connection is only possible with a crossed patch cable (Cross
cable).
We recommend using a hub that may be available in the system or using a hub that you have with you. In such
cases, the standard cabling of the CMS can be retained and the notebook can be connected to the hub using a stan-
dard network cable.
If the network is set up on the system module with single wires (terminals 8-12), the LAN socket must not be used.
If necessary, disconnect the single-wire connection before connecting the notebook to the LAN socket using a cros-
sed network cable.

5.3 Testing the connection

The initial connection to the VIBGUARD IIoT is established via the IP address assigned at the factory.
This information and other parameters for startup are included in the scope of delivery as a paper prin-
tout.
During startup, the standard IP address is to be changed and adapted to the network on-site ("Network con-
figuration" on page 16).
IP address
Subnet mask
Gateway
Username, level 3
Password, level 3
Establish a connection to the CMS.
l
Enter the IP address of the CMS in the browser. A login dialog appears.
l
Enter the login details. The CMS homepage appears following a successful login.
l
Click on <System>. The "System Menu" page appears.
l
VIBGUARD IIoT
1).
Standard network configuration
192.168.1.180
255.255.255.0
192.168.1.13
user3
user3
Commissioning