Vacuum Interrupter Integrity Test - GE Limitamp CR194 Installation Instructions Manual

Two-high vacuum control
Hide thumbs Also See for Limitamp CR194:
Table of Contents

Advertisement

CR194 Two-High Vacuum Limitamp@' Control
Step
1.
With the high-voltage
door open, push in the door op-
erated release pin as shown in Figure 39. This is not a
normal operation
and should only be used for equip-
ment check out or servicing.
Figure 39. Isolation switch handle operation
during equipment checkout
Step 2.
Push in the handle latch release shown in Figure 39
and begin to pull up on the handle. With the handle
in the intermediate
position,
push down on the top
moving armature
of the contactor.
The mechanical
in-
terlock mechanism
should prevent the armature
from
fully closing on the contactor.
Step 3.
Release the pressure
on the contactor
armature
and
move the isolation
switch handle to the full "ON" posi-
tion (i.e. the handle latch release pops back out).
Step 4.
Push down on the top of the contactor
moving arma-
ture and hold it down. The armature
should close fully
as if it were energized.
Now attempt to press the
handle latch release.
The mechanical
interlock
should
prevent the handle release from going in and you
should be unable to move the isolation
switch handle.
Step 5.
Release
the pressure
on the contactor
armature
and
operate
the isolation
switch handle to the full "OFF"
position
(i.e. the handle latch release pops back out).
Step 6.
If the mechanism
fails to meet any of the above
checks, an adjustment
must be made to the interlock
assembly as detailed
below and shown in Figure 40.
WARNING: Before making any adjustments,
be sure
that equipment
is de-energized,
the contactor
is in
handle is in an intermediate
position with the
handle latch release (Figure 39) fully depressed.
A.
B.
C.
D.
Loosen the bottom locking nut (X), Figure 40,
while holding
the top adjusting
nut (W) firmly in
position.
Also loosen the two retaining
nuts at the
top of the armature
interlock
rod (Y).
Turn the top adjusting
nut (W) until the interlock
slider is just slightly below the handle latch release
pusher rod (0.12 inches).
See Figure 42 for loca-
tion of pusher rod.
When the proper position
has been reached,
hold
the top adjusting
nut (W) and tighten
the bottom
locking nut (X) to hold the adjustment.
Finally,
tighten the two locking nuts at the top of the
armature
interlock
rod (Y).
Test the interlock
again by following
Steps 1
through
6 above.
Step 7.
Return the isolation switch handle to the "OFF" position.
Figure 40. Adjusting the interlock mechanism
V-Contactor
to paw1 engagement
W-Top
adjusting nut
Y-Armature
interlock rod
X-Bottom
locking nut
Z-Contactor
armature